How to Program
5-10 Terminal 18 Digital Input
Option:
[100] Follower AF
#2 Run
Feedback
[101] Sleep
5-11 Terminal 19 Digital Input
Option:
6
6
[0]
No Operation Functions are described under 5-1* Digital
*
5-12 Terminal 27 Digital Input
Option:
[0]
No Operation Functions are described under 5-1* Digital
*
5-13 Terminal 29 Digital Input
Option:
[0]
No Operation Functions are described under 5-1* Digital
*
5-14 Terminal 32 Digital Input
Option:
[90]
AC Contactor Functions are described under 5-1* Digital
*
5-15 Terminal 33 Digital Input
Option:
[91]
DC Contactor Functions are described under 5-1* Digital
*
5-16 Terminal X30/2 Digital Input
Option:
[0]
No operation Functions are described under 5-1* Digital
*
5-17 Terminal X30/3 Digital Input
Option:
[0]
No operation Functions are described under 5-1* Digital
*
5-18 Terminal X30/4 Digital Input
Option:
[0]
No operation Functions are described under 5-1* Digital
*
6-12
VLT Active Filter AAF 00x
Function:
Do not program this setting. It is done
automatically for paralleling. See
300-40 Master Follower Selection and
300-41 Follower ID for more infomation
about paralleling.
The filter goes into sleep mode at light
duty to save energy.
Function:
Inputs
Function:
Inputs
Function:
Inputs
Function:
Inputs
Function:
Inputs
Function:
Inputs
Function:
Inputs
Function:
Inputs
MG.90.V2.22 - VLT
5-19 Terminal 37 Safe Stop
Option:
Function:
[1]
Safe Stop
Coasts unit when safe stop is activated.
Alarm
Manual reset from LCP, digital input or Serial
*
communication bus.
[3]
Safe Stop
Coasts unit when safe stop is activated (T-37
Warning
off). When safe stop circuit is reestablished,
the unit will continue without manual reset.
[4]
PTC 1
Coasts unit when safe stop is activated.
Alarm
Manual reset from LCP, digital input or Serial
communication bus. Choice 4 is only available
when the MCB 112 PTC thermistor card is
connected.
[5]
PTC 1
Coasts unit when safe stop is activated (T-37
Warning
off). When safe stop circuit is reestablished,
the unit will continue without manual reset,
unless a digital input set to PTC Card 1 [80] is
still enabled. Choice 5 is only available when
the MCB 112 PTC thermistor card is
connected.
[6]
PTC 1 &
This choice is used when the PTC option is
Relay A
gated together with a stop button through a
safety relay to T-37. Coasts unit when safe
stop is activated. Manual reset from LCP,
digital input or Serial communication bus.
Choice 6 is only available when the MCB 112
PTC thermistor card is connected.
[7]
PTC 1 &
This choice is used when the PTC option is
Relay W
gated together with a stop button through a
safety relay to T-37. Coasts unit when safe
stop is activated (T-37 off). When safe stop
circuit is reestablished, the unit will continue
without manual reset, unless a digital input
set to PTC Card 1 [80] is (still) enabled. Choice
7 is only available when the MCB 112 PTC
thermistor card is connected.
[8]
PTC 1 &
This choice makes it possible to use a
Relay A/W
combination of alarm and warning. Choice 8
is only available when the MCB 112 PTC
thermistor card is connected.
[9]
PTC 1 &
This choice makes it possible to use a
Relay W/A
combination of alarm and warning. Choice 9
is only available when the MCB 112 PTC
thermistor card is connected.
Choices 4–9 are only available when the MCB 112 PTC
thermistor card is connected.
®