9. Technical Specifications of MAG2 and MAG4
Zones:
• MAG 2 - 2 fixed zones
• MAG 4 - 4 fixed zones
Maximum number of detectors per zone:
• Up to 20 (or 32 SensoMAG series) conventional detectors and unlimited number of
manual call points.
Thresholds for zone conditions:
• 0 ÷ 2 mA - Open circuit fault condition
• 2 ÷ 10 mA - Normal condition
• 10 ÷ 110 mA - Fire Alarm condition
• 110 mA - Short circuit condition
Power supply:
• Main Power supply: 230V AC ±10%; 0.315A fuse
• Standby Power supply: 1 x 12V / 7Ah; 2A fuse
• Internal resistance of accumulator battery: Ri < 1.6Ω
Maximum current available for system devices (with fully charged battery):
• 0.7 A
Current consumption - mains failure:
• 50 mA
Outputs:
• Sounder Circuit 1: 24V / 0.3A; 0.3A fuse (PTC)
• Sounder Circuit 2: 24V / 0.3A; 0.3A fuse (PTC)
• Fault Relay, volt free changeover contacts*: 3A @ 120V AC; 3A @ 60V DC
• Fire Relay, volt free changeover contacts*: 3A @ 120V AC; 3A @ 60V DC
*
Note: These functions may not be used to provide any "Options with requirements" as specified
in EN 54-2.
Auxiliary output:
• 24V DC, 0.3A fuse (PTC)
Cabling:
• Maximum 2.5mm diameter
Environment:
• Working temperature: -5 to 40°C
• Storage temperature: -20 to 60°C
• Humidity: 0 to 95%
Temperature sensor:
The temperature sensor is used for measurement of the battery temperature. The sensor
is mounted at the end of the wired fly lead, factory connected to "Temperature sensor"
terminal on the panel's PCB.
The temperature sensor should be placed behind or under the battery.