iRIS4 - Addressable Fire Alarm Panel – Installation Manual

1.3.1. General Technical Specifications

Loops - from 1 to 4 loops
Up to 250 devices per one iRIS8 TTE Loop expander
Max. number of devices - 1000
Zone Number - 96 max.
Zone Groups - 48 max.
TTE Communication protocol
Memory log for 10000 events
Monitored relay outputs - 4:
o
SND (for connection sounder) - 24VDC/0.5A
Fire R (Fire Alarm) – 24VDC / 0.1A
o
o
Fire P (Fire Protection) - 24VDC / 0.1A
o
Fault R (Fault) - 24VDC / 0.1A
Non monitored relay outputs:
o
4 programmable - 15A@24VDC
Auxiliary output (terminals +24V and GND - see item 4.2.1) – 24VA@0.3A
Display – 5 inch 800/480 TFT
Real time clock
Up to 250 programmable Inputs/Outputs per panel
Comprehensive day/night mode facility
2 Steps of alarm levels (T1 and T2)
Automatic synchronization of all loop sounders for better alarm signal
Based on Windows graphical configuration utility via Ethernet or USB
Simple Http monitoring utility
Loop less and Output less panel option (repeater)
Thermal printer (optional)
PASO panel (optional)
Multi-language support
Easy software update
Cloud ready (from SW1.1.1 and aboveiRIS8)
Certified according EN 54-2/4

1.3.2. Working Environment

IP30
Operation temperature: -5ºС up to +40ºC
Relative humidity: up to 95% (without condense)
Storage temperature: -10ºС up to +50ºC
Weight (without battery): ~6 kg
Dimensions: 430x330x120 mm

1.3.3. Electrical Characteristics

Cable: 4-wire
Cross section: 0.25mm
Up to 1000m long distance
Earth Connection
The earth connection has to be realized in accordance with the rules for the electrical safety with the total resistance in
the circuit lower than 10Ω. It is mandatory to connect the main power supply cable to the middle input of the fire panel
terminal – see also item
2
4.1
Main Power Supply connection.
ATTENTION: The total current
consumption of outputs +24V,
SND, Fire R, Fire P and Fault R
must not exceed 0.5A!