iRIS4 - Addressable Fire Alarm Panel – Installation Manual
1.3.1. General Technical Specifications
•
Loops - from 1 to 4 loops
•
Up to 250 devices per one iRIS8 TTE Loop expander
•
Max. number of devices - 1000
•
Zone Number - 96 max.
•
Zone Groups - 48 max.
•
TTE Communication protocol
•
Memory log for 10000 events
•
Monitored relay outputs - 4:
o
SND (for connection sounder) - 24VDC/0.5A
Fire R (Fire Alarm) – 24VDC / 0.1A
o
o
Fire P (Fire Protection) - 24VDC / 0.1A
o
Fault R (Fault) - 24VDC / 0.1A
•
Non monitored relay outputs:
o
4 programmable - 15A@24VDC
•
Auxiliary output (terminals +24V and GND - see item 4.2.1) – 24VA@0.3A
•
Display – 5 inch 800/480 TFT
•
Real time clock
•
Up to 250 programmable Inputs/Outputs per panel
•
Comprehensive day/night mode facility
•
2 Steps of alarm levels (T1 and T2)
•
Automatic synchronization of all loop sounders for better alarm signal
•
Based on Windows graphical configuration utility via Ethernet or USB
•
Simple Http monitoring utility
•
Loop less and Output less panel option (repeater)
•
Thermal printer (optional)
•
PASO panel (optional)
•
Multi-language support
•
Easy software update
•
Cloud ready (from SW1.1.1 and aboveiRIS8)
•
Certified according EN 54-2/4
1.3.2. Working Environment
•
IP30
•
Operation temperature: -5ºС up to +40ºC
•
Relative humidity: up to 95% (without condense)
•
Storage temperature: -10ºС up to +50ºC
•
Weight (without battery): ~6 kg
•
Dimensions: 430x330x120 mm
1.3.3. Electrical Characteristics
•
Cable: 4-wire
•
Cross section: 0.25mm
•
Up to 1000m long distance
Earth Connection
The earth connection has to be realized in accordance with the rules for the electrical safety with the total resistance in
the circuit lower than 10Ω. It is mandatory to connect the main power supply cable to the middle input of the fire panel
terminal – see also item
2
4.1
Main Power Supply connection.
ATTENTION: The total current
consumption of outputs +24V,
SND, Fire R, Fire P and Fault R
must not exceed 0.5A!
6