One Man" Zone Testing - Teletek electronics MAG2 User Manual

Fire control panel
Table of Contents

Advertisement

• Press RESET:
You can exit the sounder disabling mode also by pressing the "TEST/ SCROLL" button,
as in that case the you reject the procedure.
Z
To enable the sounders:
• Press ENABLE/ DISABLE:
• Press TEST/ SCROLL, until
you reach the last zone in the
system:
• Press ENABLE/ DISABLE:
• Press RESET:
You can exit the sounder enabling mode also by pressing the "TEST/ SCROLL" button,
as in that case the you reject the procedure.

8.2 "One man" Zone Testing

The "One Man" Test mode gives the installer the possibility to test the efficiency of the
system - whether the detectors react to smoke, heat, etc.
Z
To do "One Man" Test of a zone:
• Press TEST/ SCROLL:
• Press TEST/ SCROLL again:
• Press TEST/ SCROLL again to
continue with the system testing:
Continue the system testing by pressing the "TEST/ SCROLL" button. The exit from the
"One Man" Test mode is automatic after the end of the test procedure in the last Zone 4,
or at any time by pressing "RESET" button.
Fire Control Panel MAG2/4 - User Manual
The SOUNDER FAULT/DISABLE and ENABLE/
DISABLE LEDs light up permanently.
At this step the sounders are disabled.
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
The SOUNDER FAULT/DISABLE LED lights up
permanently.
The SOUNDER FAULT/DISABLE LED will start
blinking.
At this step the sounders are enabled.
µP Fault and General Fault LEDs light off. All other
system indication LEDs light on permanently.
The TEST LED and ZONE 1 yellow LED start
blinking.
ZONE 1 is in test mode. Test a detector from this
zone whether it react to smoke, heat, etc.
TEST LED will continue blinking.
The ZONE 1 yellow LED lights out (the zone is
not longer in test mode). The ZONE 2 yellow LED
blinks in yellow.
ZONE 2 is in test mode. Test a detector from this
zone whether it react to smoke, heat, etc.
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag4

Table of Contents