Operation Instructions; Zone Enabling/ Disabling; Sounders Enabling/ Disabling - Teletek electronics MAG2 User Manual

Fire control panel
Table of Contents

Advertisement

8. Operation instructions

8.1 Zone Enabling/ Disabling

Z
To disable a zone:
• Press ENABLE/ DISABLE:
• Press TEST/ SCROLL, until
you reach the zone which has to
be disabled:
• Press ENABLE/ DISABLE:
• Press RESET:
Z
To enable a zone:
• Press ENABLE/ DISABLE:
• Press TEST/SCROLL, until you
reach the zone which has to en-
able:
• Press ENABLE/ DISABLE:
• Press RESET:

8.2 sounders Enabling/ Disabling

!
A sound signalization is activated at every service Mode entering. The
signalization is off by pressing "sILENCE BUZZER" button.
Z
To disable the sounders:
• Press ENABLE/ DISABLE:
• Press TEST/ SCROLL, until
you reach the last zone in the
system:
• Press ENABLE/ DISABLE:
10
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
The respective zone yellow LED blinks.
The yellow LED of the disabled zone lights up per-
manently.
At this step the zone is disabled.
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
The yellow LED of the disabled zone lights up per-
manently.
The yellow LED of the enabled zone blinks.
At this step the zone is enabled.
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
The SOUNDER FAULT/DISABLE LED will start
blinking.
The SOUNDER FAULT/DISABLE LED lights up
permanently.