Changing local setpoint
1, 2, or 3
4/00
Use the procedure in Table 5-11 to change any of the local setpoint
values.
After changing a local setpoint value, if no other key is pressed, a
minimum of 30 seconds time will elapse before the new value is stored in
nonvolatile memory. If power is removed before this time, the new
setpoint value is lost and the previous setpoint value is used at power up.
If after changing the LSP value another key is pressed, then the value is
stored immediately.
Table 5-11
Procedure for Changing the Local Setpoints
Step
Operation
1
Select the
setpoint
2
Select a different
setpoint or the
remote setpoint
3
Change the
value
UDC 3300 Controller Product Manual
Press
until you see
SETPOINT
SELECT
Upper Display
Lower Display
to cycle through the setpoint type menu as
SETPOINT
long as the key is pressed. When the key is
SELECT
released, the setpoint selection currently
displayed will be the new setpoint selection.
and hold
in
to change the local setpoint to the value at
or
which you want the process maintained.
SP, 2SP, or 3SP indicator will light to match
the lower display.
ATTENTION
cannot be changed at the keyboard.
Action
The PV value
SP, 2SP, or 3SP and
the local setpoint value
or RSP and the remote
setpoint value
The remote setpoint
161