Honeywell UDC 3300 Product Manual page 71

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

Function Prompt
Lower Display
OUT RATE
Output Change Rate
ATTENTION
Does not apply to 3
Position Step
Control algorithm.
PCT/M UP
Output Rate Up Value
PCT/M DN
Output Rate Down Value
OUTHiLIM
High Output Limit
OUTLoLIM
Low Output Limit
I Hi LIM
High Reset Limit
I Lo LIM
Low Reset Limit
DROPOFF
Controller Dropoff Value
DEADBAND
Output Relay Deadband
OUT HYST
Output Relay Hysteresis
FAILMODE
Failsafe Mode
FAILSAFE
Failsafe Output Value for all
outputs except 3P Step
Failsafe Output Value for 3P
Step
SW_FAIL
PDMR/Position Proportional
motor position when
slidewire fails
MAN OUT
Power-up Preset Output for
Manual Output
AUTO OUT
Power-up Preset Output for
Automatic Output
PBorGAIN
Proportional Band or
Gain Units
MINorRPM
Reset Units
4/00
Function
Name
ENABLE
DISABL
0 to 9999 % per minute
0 to 9999 % per minute
–5.0 to 105 % of output
–5.0 to 105 % of output
Within the range of the output limits
Within the range of the output limits
–5 to 105 % of output
Time Duplex:
–5.0 to 25.0 %
On/Off Duplex:
0.0 to 25.0 %
Position Prop. and 3P Step:
0.5 to 5.0 %
0.0 to 100.0 % of PV Span for On/Off
control.
NO LAT
LATCH
Set within the range of the output
limits. 0 to 100 %
0 PCT (motor goes to closed position)
100PCT (motor goes to open position)
0 PCT (motor goes to closed position)
100PCT (motor goes to open position)
Within the range of output limits
Within the range of output limits
PB PCT
GAIN
RPM
MIN
UDC 3300 Process Controller Product Manual
Selections or
Range of Setting
Upper Display
Factory
Refer
Setting
to
Section
DISABL
4.11
0
0
100
0.0
100.0
0.0
0
1.0
0.5
NO LAT
0.0
- -
- -
- -
GAIN
MIN
59