Honeywell UDC 3300 Product Manual page 99

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

Lower Display
Prompt
EU/HRDN2
SP PROG
(option)
4/00
Upper Display
Range of Setting
or Selection
0 to 9999 engineering units
per hour
DISABL
ENABLE
ENABL2
ENAB12
UDC 3300 Process Controller Product Manual
Parameter
Definition
RATE DOWN—Rate down value for Loop 2. When
making a setpoint change, this is the rate at which the
controller will change from the original setpoint down to
the new one. The ramping (current) setpoint can be
viewed as SPn in the lower display.
Entering a 0 will imply an immediate change in Setpoint
(i.e., no rate applies).
SETPOINT RAMP/SOAK PROGRAM—Available only
with controllers that contain this option.
SP RAMP and SP RATE must be disabled.
DISABLE—Disables setpoint programming.
ENABLE—Enables setpoint programming for Loop1 only.
ENABL2—Enables setpoint programming for Loop 2 only.
ENAB12—Enables setpoint programming for both Loop 1
and Loop 2.
For reasons of convenience, the information for the
prompts when SP PROG is enabled are included in
Section 6 – Setpoint Programming Option.
87