Lower Display
Prompt
OUT2 ALG
RLYSTATE
RLY TYPE
4/00
Upper Display
Range of Setting
or Selection
NONE
TIME
CURRNT
CUR D
CUR TI
TI CUR
1OF2OF
1ON2OF
1OF2ON
1ON2ON
MECHAN
SOL ST
UDC 3300 Process Controller Product Manual
Parameter
Definition
The OUTPUT ALGORITHM lets you select the type of
output you want for the second control loop
See OUT ALG for definitions.
NONE
TIME SIMPLEX
CURRENT SIMPLEX (AUX OUT)
CURRENT DUPLEX (AUX OUT)
CURRENT/TIME DUPLEX
TIME/CURRENT DUPLEX
ATTENTION If Time Duplex or TPSC is selected as the
first control loop output, then TIME, CUR TI, and TI CUR
are not available as the second control loop output.
DIGITAL OUTPUT STATUS AT 0 % OUTPUT allows the
following selections:
1OF2OF
Output 1 de-energized
Output 2 de-energized
1ON2OF
Output 1 energized
Output 2 de-energized
1OF2ON
Output 1 de-energized
Output 2 energized
1ON2ON
Output 1 energized
Output 2 energized
RELAY CYCLE TIME INCREMENT selection is used only
for Time Simplex and Duplex output configurations and
affects both loops. This configuration sets the increment
size of the relay cycle times in the Tuning and Tuning 2
Set Up groups.
ELECTROMECHANICAL RELAY—Cycle time in one-
second increments.
SOLID STATE RELAY—Cycle time in 1/3 second
increments. This is useful for solid state relay applications
that require shorter cycle times. DO NOT use this setting
unless cycle times of less than 1 second are required.
The Lockout selection must be set to NONE in order to
view this selection.
111