Alarm Setpoints; Table 4-5 Procedure For Displaying Alarm Setpoints - Honeywell UDC2500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

4.7 Alarm Setpoints

Introduction
An alarm consists of a relay contact and an operator interface indication. The alarm relay
is de-energized if setpoint 1 or setpoint 2 is exceeded.
The alarm relay is energized when the monitored value goes into the allowed region by
more than the hysteresis.
The relay contacts can be wired for normally open (NO) energized or normally closed
(NC) de-energized using internal jumper placement. See Table 2-3 in the Section 2 –
Installation for alarm relay contact information.
There are four alarm setpoints, two for each alarm. The type and state (High or Low) is
selected during configuration. See Subsection 3– Configuration for details.
Alarm Setpoints Display

Table 4-5 Procedure for Displaying Alarm Setpoints

Step
Operation
1
Select Alarm
Set-up Group
2
Access the Alarm
Setpoint Values
Change a value
3
4
Return to Normal
Display
Press
Until you see:
SET UP
Upper Display = SET
Lower Display = ALARMS
To successively display the alarm setpoints and their values.
FUNCTION
Their order of appearance is shown below.
Upper Display = (the alarm setpoint value)
Range values are within the range of the selected
parameters:
DE (Deviation) value = within Input 1 Span
PV (Process variable) value = Within Input 1 range
To change any alarm setpoint value in the upper display
or
LOWER
DISPLAY
UDC2500 Universal Digital Limit ControllerProduct Manual
Operating the Limit Controller
Result
57

Advertisement

Table of Contents
loading

Table of Contents