Lower Display
Prompt
XMITTER
ANALYTIC*
* Expanded models only
IN1 HI
4/00
Upper Display
Range of Setting
or Selection
Select one from the columns
below
B TC
S TC
E TC H
T TC H
E TC L
T TC L
J TC H
W TC H
J TC L
W TC L
K TC H
100 PT
K TC L
100 LO
NNM H
200 PT
NNM L
500 PT
NM90 H
RAD RH
NM90 L
RAD RI
NIC TC
LINEAR
R TC
SQROOT
ANALYTIC
NONE
PH
ORP mV
CONDmS
CONDuS
RSTVM^
TDS PPm
TDS PPb
CONCPt
DO PPm
DO PPb
–999. To 9999. Floating
(in engineering units)
UDC 3300 Process Controller Product Manual
Parameter
Definition
TRANSMITTER CHARACTERIZATION—This selection
lets you instruct the controller to characterize a linear input
to represent a non-linear one.
ATTENTION Prompt only appears when a linear
actuation is selected at prompt IN1 TYPE.
FOR EXAMPLE:
If input 1 is a 4 to 20 mA signal, but the signal represents
a type K thermocouple, select K TC H and the controller
will characterize the 4 to 20 mA signal so that it is treated
as a type K thermocouple input (high range).
Parameter definitions are the same as in IN1 TYPE.
Analytic Input Selections and Ranges—This prompt
appears only when XMITTER is set to ANALYTIC.
Choosing an Analytic setting here will set the Input Range
to appropriate Hi and Low values for that analytical
application. You can adjust the Input Range if you want.
Input Hi
NONE
as configured
pH
14.00
ORP
1600
(millivolts)
CONDUCTIVITY
20.00
(milli Siemens)
CONDUCTIVITY
2000
(micro Siemens)
RESISTIVITY
2000
(Megaohms)
TOTAL DISSOLVED SOLIDS 9999
(parts per million)
TOTAL DISSOLVED SOLIDS 9999
(parts per billion)
CONCENTRATION
20.00
(parts per thousand)
DISSOLVED OXYGEN
20.00
(parts per million)
DISSOLVED OXYGEN
2000
(parts per billion)
INPUT 1 HIGH RANGE VALUE in engineering units is
displayed for all inputs but can only be configured for
linear or square root transmitter characterization.
Scale the #1 input signal to the display value you want for
100 %.
EXAMPLE:
Actuation (Input) = 4 to 20 mA
Process Variable = Flow
Range of Flow = 0 to 250 Gal/Min
High Range display value = 250
Then 20 mA = 250 Gal/Min
The control setpoint will be limited by the range of units
selected here.
Input Low
as configured
0.00
–999
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
113