Honeywell UDC 3300 Product Manual page 117

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

Lower Display
Prompt
8SEG CH2
ATTENTION The X values below should be entered as increasing values (from 0% to 100%) from N=0 to 8.
X0 VALU2
X1 VALU2
X2 VALU2
X3 VALU2
X4 VALU2
X5 VALU2
X6 VALU2
X7 VALU2
X8 VALU2
Y0 VALU2
Y1 VALU2
Y2 VALU2
Y3 VALU2
Y4 VALU2
Y5 VALU2
Y6 VALU2
Y7 VALU2
Y8 VALU2
4/00
Upper Display
Range of Setting
or Selection
DISABL
INPUT1
INPUT2
L1 OUT
L2 OUT
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
UDC 3300 Process Controller Product Manual
Parameter
Definition
8 SEGMENT CHARACTERIZER #2—A second eight
segment characterizer can be applied to either
Input 1, Input 2, Output 1, or Output 2.
DISABLE—Disables characterizer.
INPUT 1—Characterizer applied to Input 1.
INPUT 2—Characterizer applied to Input 2.
LOOP 1 OUTPUT—Characterizer applied to Loop 1
Output. (NOTE 1)
LOOP 2 OUTPUT—Characterizer applied to Loop 2
Output.
There are eight (Xn) Input values and eight (Yn) Output
values to be selected. The following rules apply:
• When Input 2 is used, Input 2 Ratio and Bias are
applied to the Xn Values.
• When one of the Loop outputs are selected, the Xn
Input values are the Output from the control algorithm,
and the Yn Output is the final control element action.
This application is useful for non-linear control elements
or Process Variable.
A simple example is shown in Figure 4-2.
X0 INPUT VALUE (X AXIS)
X1 INPUT VALUE (X AXIS)
X2 INPUT VALUE (X AXIS)
X3 INPUT VALUE (X AXIS)
X4 INPUT VALUE (X AXIS)
X5 INPUT VALUE (X AXIS)
X6 INPUT VALUE (X AXIS)
X7 INPUT VALUE (X AXIS)
X8 INPUT VALUE (X AXIS)
Y0 INPUT VALUE (Y AXIS)
Y1 INPUT VALUE (Y AXIS)
Y2 INPUT VALUE (Y AXIS)
Y3 INPUT VALUE (Y AXIS)
Y4 INPUT VALUE (Y AXIS)
Y5 INPUT VALUE (Y AXIS)
Y6 INPUT VALUE (Y AXIS)
Y7 INPUT VALUE (Y AXIS)
Y8 INPUT VALUE (Y AXIS)