Honeywell UDC 3300 Product Manual page 116

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

Table 4-5
Lower Display
Prompt
8SEG CH1
ATTENTION The X values below should be entered as increasing values (from 0% to 100%) from N = 0 to 8.
X0 VALUE
X1 VALUE
X2 VALUE
X3 VALUE
X4 VALUE
X5 VALUE
X6 VALUE
X7 VALUE
X8 VALUE
Y0 VALUE
Y1 VALUE
Y2 VALUE
Y3 VALUE
Y4 VALUE
Y5 VALUE
Y6 VALUE
Y7 VALUE
Y8 VALUE
104
Algorithm Group Definitions, Continued
Upper Display
Range of Setting
or Selection
DISABL
INPUT1
INPUT2
L1 OUT
L2 OUT
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
UDC 3300 Process Controller Product Manual
Parameter
Definition
8 SEGMENT CHARACTERIZER #1—An eight segment
characterizer can be applied to either Input 1, Input 2,
Output 1, or Output 2.
DISABLE—Disables characterizer.
INPUT 1—Characterizer is applied to Input 1.
INPUT 2—Characterizer is applied to Input 2.
LOOP 1 OUTPUT—Characterizer is applied to Loop 1
Output. (NOTE 1)
LOOP 2 OUTPUT—Characterizer is applied to Loop 2
Output.
There are eight (Xn) Input values and eight (Yn) Output
values to be selected. The following rules apply:
• When Input 2 is used, Input 2 Ratio and Bias are
applied to the Xn Values.
• When one of the Loop outputs are selected, the Xn
Input values are the Output from the control algorithm,
and the Yn Output is the final control element action.
This application is useful for non-linear control elements
or Process Variable.
A simple example is shown in Figure 4-2.
X0 INPUT VALUE (X AXIS)
X1 INPUT VALUE (X AXIS)
X2 INPUT VALUE (X AXIS)
X3 INPUT VALUE (X AXIS)
X4 INPUT VALUE (X AXIS)
X5 INPUT VALUE (X AXIS)
X6 INPUT VALUE (X AXIS)
X7 INPUT VALUE (X AXIS)
X8 INPUT VALUE (X AXIS)
Y0 INPUT VALUE (Y AXIS)
Y1 INPUT VALUE (Y AXIS)
Y2 INPUT VALUE (Y AXIS)
Y3 INPUT VALUE (Y AXIS)
Y4 INPUT VALUE (Y AXIS)
Y5 INPUT VALUE (Y AXIS)
Y6 INPUT VALUE (Y AXIS)
Y7 INPUT VALUE (Y AXIS)
Y8 INPUT VALUE (Y AXIS)