Honeywell UDC 3300 Product Manual page 146

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

Lower Display
Prompt
DIG IN 1
(continued)
DIG 1 COM
DIG IN 2
DIG2 COM
*For the Output Tracking selections, when the switch is open, the output is in accordance with its pre-defined
functionality. When the switch is closed, the output value (in percent) will track the Input 2 percent of range value.
When the switch is reopened, the output will start at this last output value and normal PID action will then take over
control. The transfer is bumpless.
NOTE 1: Does not apply to Three Position Step Control.
134
Upper Display
Range of Setting
or Selection
HealthWatch option prompts:
RESETT1
RESETT2
RESETT3
R ALL T
RESETC1
RESETC2
RESETC3
R ALL C
RALLTC
DISABL
+PID2
+ToDIR
+ToSP2
+DISAT
+ToSP1
+RUN
Same selections as for
Digital Input 1
Same selections as Digital
Input 1 Combinations
UDC 3300 Process Controller Product Manual
Parameter
Definition
TIMER 1 will be reset when contact closes.
TIMER 2 will be reset when contact closes.
TIMER 3 will be reset when contact closes.
ALL TIMERS will be reset when contact closes.
COUNTER 1 will be reset when contact closes.
COUNTER 2 will be reset when contact closes.
COUNTER 3 will be reset when contact closes.
ALL COUNTERS will be reset when contact closes.
ALL TIMERS AND COUNTERS will be reset when
contact closes.
DIGITAL INPUT 1 COMBINATION SELECTIONS — All
selections are available in combination with Input 1.
DISABLE—Disables combination function.
Any Digital Input Selection PLUS PID2—Contact
closure selects PID Set 2.
Any Digital Input Selection PLUS DIRECT ACTION—
Contact closure selects direct controller action.
Any Digital Input Selection PLUS SETPOINT 2—
Contact closure puts the controller into setpoint 2.
Any Digital Input Selection PLUS DISABLE ADAPTIVE
TUNE—Contact closure disables Accutune process on
Loop 1.
Any Digital Input Selection PLUS SETPOINT 1—
Contact closure puts the controller into setpoint 1.
Any Digital Input Selection PLUS RUN SETPOINT
PROGRAM/RAMP—Contact closure starts SP
Program/Ramp if enabled.
DIGITAL INPUT 2 SELECTIONS
DIGITAL INPUT 2 COMBINATIONS