Mitsubishi Electric MELSEC iQ-R C R12CCPU-V User Manual page 187

Controller module
Hide thumbs Also See for MELSEC iQ-R C R12CCPU-V:
Table of Contents

Advertisement

Error
Error name
Error details and cause
code
21A1H
File
The file specified in parameter cannot be
specification
created.
error
2200H
Parameter
The system parameter file and CPU
error
parameter file do not exist.
2220H
Parameter
The parameter setting is corrupted.
error
2221H
Parameter
The set value is out of range.
error
2222H
Parameter
Use of the function that is not supported by
error
the module is enabled.
2224H
Parameter
A memory area cannot be ensured.
error
2225H
Parameter
• The model type (CPU module name) set
error
with CW Configurator differs from that of
the CPU module actually mounted.
• The operation set in the memory card
parameters cannot be performed.
(The boot function cannot be executed.)
Corrective action
• Check the detailed information (parameter
information) of the error by performing module
diagnostics using CW Configurator, and correct
the name and size of the file corresponding to the
displayed number (parameter number).
• Check the detailed information (drive and file
information) of the error by performing module
diagnostics using CW Configurator, and take any
of the following action.
(1) Format the corresponding drive.
(2) Delete unnecessary files on the corresponding
drive to increase free space.
(3) Unlock the corresponding drive if it is locked.
Write the system parameter and CPU parameter.
Check the detailed information (parameter
information) of the error by performing module
diagnostics using CW Configurator, and write the
displayed parameter to the module. If the same error
code is displayed again, the possible cause is a
hardware failure of the data memory in the CPU
module, memory card, I/O module, or intelligent
function module. Please consult your local
Mitsubishi representative.
Check the detailed information (parameter
information) of the error by performing module
diagnostics using CW Configurator, and review the
parameter setting corresponding to the displayed
number (parameter number). If the same error code
is displayed again, the possible cause is a hardware
failure of the data memory in the CPU module,
memory card, I/O module, or intelligent function
module. Please consult your local Mitsubishi
representative.
Check the detailed information (parameter
information) of the error by performing module
diagnostics using CW Configurator, and review the
parameter setting corresponding to the displayed
number (parameter number). If the same error code
is displayed again, the possible cause is a hardware
failure of the data memory in the CPU module,
memory card, I/O module, or intelligent function
module. Please consult your local Mitsubishi
representative.
Check the detailed information (parameter
information) of the error by performing module
diagnostics using CW Configurator, increase the
capacity of the area corresponding to the displayed
parameter with error jump. (If the capacity of the
area cannot be increased, decrease the capacity of
other areas.)
• Correct the model type (CPU module name) set to
the CW Configurator project in accordance with
the CPU module actually mounted.
• Delete the memory card parameters.
• Remove the memory card so that the operation
set in the memory card parameters will not be
performed. (Do not execute the boot operation.)
Detailed
Diagnosti
informati
c timing
on
Drive and
At write,
file
power ON,
information
or RESET
Parameter
information
Parameter
At power
information
ON or
RESET
Parameter
At power
information
ON or
RESET
Parameter
At power
information
ON, RESET,
fixed cycle
processing
execution,
instruction
execution,
or module
access
Parameter
At power
information
ON or
RESET
Parameter
At write,
information
power ON,
or RESET
Parameter
At write,
information
power ON,
or RESET
APPX
Appendix 1 Error Code List
A
185

Advertisement

Table of Contents
loading