Error
Error name
Error details and cause
code
2520H
Invalid interrupt
Even though an interrupt was requested,
there is no interrupt factor.
2521H
Invalid interrupt
Even though an interrupt was requested,
there is no interrupt factor.
2522H
Invalid interrupt
An interrupt request from the module with
no interrupt setting has been detected.
2610H
Inter-module
• An execution interval error of the
synchronization
synchronous interrupt program was
signal error
detected.
• An inter-module synchronization error
was detected.
2611H
Inter-module
An inter-module synchronization error was
synchronization
detected.
signal error
2630H
Multiple CPU
• An execution interval error of the
synchronization
synchronous interrupt program was
signal error
detected.
• A multiple CPU synchronization error
was detected.
2631H
Multiple CPU
A multiple CPU synchronization error was
synchronization
detected.
signal error
3000H
Boot function
The boot setting in the memory card
execution error
parameters is incorrect.
3001H
Boot function
When the boot function was executed, the
execution error
file format processing failed.
3004H
Boot function
When the boot function was executed, the
execution error
CPU built-in memory capacity was
exceeded.
Corrective action
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, or base unit. Please consult your
local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, or base unit. Please consult your
local Mitsubishi representative.
• Review the interrupt setting in the module
parameter.
• Take measures so that no interrupt is requested
from the module with no interrupt setting exists in
the module parameter.
• Review the interrupt setting in the buffer memory
of the Intelligent function module.
• When the CC-Link IE Field Network module is a
synchronous target unit between unit, check the
connection status of the cable of CC-Link IE Field
module.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, base unit, or extension cable.
Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, base unit, or extension cable.
Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module or base unit. Please
consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module or base unit. Please
consult your local Mitsubishi representative.
Review the boot setting in the memory card
parameters.
Reset the CPU module and perform the boot
function again. If the same error code is displayed
again, the possible cause is a hardware failure of the
CPU module. Please consult your local Mitsubishi
representative.
• Review the boot setting.
• Delete unnecessary files in the CPU built-in
memory.
Detailed
Diagnosti
informati
c timing
on
System
At interrupt
configuratio
occurrence
n
information
At interrupt
occurrence
System
At interrupt
configuratio
occurrence
n
information
Always
System
At power
configuratio
ON, RESET,
n
or fixed
information
cycle
processing
execution
Always
System
At power
configuratio
ON, RESET,
n
or fixed
information
cycle
processing
execution
Drive and
At power
file
ON or
information
RESET
Drive and
At power
file
ON or
information
RESET
Drive and
At power
file
ON or
information
RESET
APPX
Appendix 1 Error Code List
A
191

Advertisement

Table of Contents
loading

Table of Contents