Mitsubishi Electric MELSEC iQ-R C R12CCPU-V User Manual page 114

Controller module
Hide thumbs Also See for MELSEC iQ-R C R12CCPU-V:
Table of Contents

Advertisement

■Processing points for Test (random write)
Set the processing points within the value which can be acquired with the following formula.
(Number of word access points) × 12 + (Number of double word access points) × 14 ≤ 1920
• For bit devices, 1-point equals 16-bit for word access. As for double word access, 1-point equals 32-bit.
• For word devices, 1-point equal 1-word for word access. As for double word access, 1-point equal 2-word.
Available devices
The available devices are as follows.
Device
I/O device
Internal user device
Internal system device
*1 ASCII code cannot be used.
6 Ethernet COMMUNICATION FUNCTIONS
112
6.2 Communication with SLMP
Device code
Input
9CH
Output
9DH
Internal relay
90H
Data register
A8H
Link relay
A0H
Link register
B4H
Special relay
91H
Special register
A9H
*1
Device number range
0H to FFFH
0H to FFFH
Device number within the range in the C Controller module of the
target station can be specified.
0 to 2047
0 to 2047
Hex
Hex
Dec
Dec
Hex
Hex
Dec
Dec