■Link scan setting
Set timeout time and number of retries for slave station disconnection detection.
The parameter is used as an initial parameter. By using a C Controller dedicated function, the initial parameter
can be changed dynamically. (Page 137 Parameter change example)
Window
Displayed items
Item
Slave Station
Time-out Period
Disconnection
(10 to 65535)
Detection Setting
Counts
Slave Station
Disconnection
Detection Image
Display
*1 Timeout time and the number of times for disconnection detection are counted for each slave station.
*2 Disconnection occurs in the event that no response is received from the slave station for the specified number of times in succession
within the timeout time.
• Set an adequate value for the timeout time according to the actual system used.
• Time-out Period and Counts can be set for each group.
Description
Set the timeout time (ms) for slave station disconnection
*1
detection.
Set the number of retries for slave station disconnection
*1,*2
detection.
The operation image regarding the slave station disconnection
detection period is displayed. Refer to this at the setting of "Time-
out Period".
Setting range
10 to 65535 ms
3 Times, 5 Times, 10
Times
7 CC-Link IE Field Network Basic FUNCTION
7.3 Parameter Settings
Default
100 ms
7
3 Times
141