How To Assign Parameters In Db1 Without Com 95F; Rules For Setting Parameters In Db1 - Siemens SIMATIC S5-95F Manual

Table of Contents

Advertisement

S5-95F
9.3.2

How to Assign Parameters in DB1 without COM 95F

Use the following steps to change or expand the preset values of DB1:
Display the default DB1 on the programmer.
Position the cursor on the desired parameter block.
Change or expand the parameters.
(for an explanation and possible parameter values see section 9.3.6)
Transfer the changed DB1 to the programmable controller.
Switch the programmable controller from STOP to RUN.
Changed DB1 parameters are accepted. For all settings that are not changed, the default settings
remain valid. The default settings are selected so that the S5-95F assumes a status as safe as
possible.
Note
If the programmable controller recognizes a parameter error in DB1, the S5-95F enters
the cause of the error in the system event DB (error No. 70 "Parameter assignment
error in DB1"). The S5-95F does not go to RUN.
9.3.3

Rules for Setting Parameters in DB1

DB1 consists of the following:
A start block ID
One or more parameter blocks . . . . . . . . . . . . . . . . . . . .
A parameter block consists of:
A block end symbol
EWA 4NEB 812 6210-02
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A block ID . . . . . . . . . . . . . . . . . . . . . . . . .
One or more parameters
A parameter consists of:
A parameter name . . . . . . . . . . .
One or more arguments . . . . . . .
A block end ID . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blocks and Their Functions
DB1
e.g.: OBC: CAP 7 500
e.g.: OBC:
. . . . . . . . . . . . . .
e.g.: CAP 7 500
e.g.: CAP
e.g.: 7 500
: ; (Semicolon)
: END
9-27