Module Spectrum
Analog Output Module 2 x±10 V (continued)
Technical Specifications
Output range
(rated values)
Number of outputs
Galvanic isolation
Input resistance
Capacitive load incl.
cable capacitance
Connection method
Digital representation
of output signal
Measured value
representation
Conversion time
(0 to 100 %)
Permissible overload
Short-circuit protection
Short-circuit current
Permissible voltage
difference to ground
and between outputs
Basic error limits
(operational error limits
at 25 °C (77 °F), referred to
output range of the module)
Operational error limits
(0 to 60 °C (32 to 140 °F),
referred to output range)
Length of cable
- shielded
Supply voltage L+
(peripheral)
- rated value
- ripple V
PP
- permissible range
(ripple included)
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(Output to L +, between
outputs, output to + 9 V)
- insulation group
- tested with
Current consumption
- from + 9 V (CPU)
- from L +
Power loss
of the module
Weight
A-26
±10 V
2
yes (outputs to
grounding point and
between outputs)
3.3 k
<100 nF
two- or four-wire
connection
11 bits + sign
(1024 units =
rated value)
two's complement
(left-justified)
max.
0.15 ms
25 %
yes
±30 mA
max.
75 V DC/60 V AC
±0.3 %
±0.6 %
max.
200 m (600 ft.)
24 V DC
3.6 V
20 to 30 V
12 V AC
1 x B
500 V AC
60 V AC
1 x B
500 V AC
typ.
170 mA
typ.
100 mA
typ.
3.1 W
approx.
290 g (10 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
tested with
Electromagnetic fields
to IEC 801-3
tested with
Fast transient burst
to IEC 801-4
tested with
S5-95F
(6ES5 470-8MA12)
Severity rating 2
8 kV air discharge
4 kV contact discharge
Severity rating 2
3 V / m
Severity rating 3
2 kV on supply lines
1 kV on signal lines
EWA 4NEB 812 6210-02