S5-95F
Parameter
Argument
Block ID: OBDE
Default setting
DE
32.X S
DE
33.X S
Permissible changes
DE
32.x t
DE
33.x t
EWA 4NEB 812 6210-02
Discrepancy time for onboard inputs
All (non-interrupt) onboard inputs have the short discrepancy
time as default setting.
The discrepancy time can be changed for each onboard input.
Permissible range of values
Bit no. x:
x = 0, 1, ... 7, X
(X: all bits)
Discrepancy time t:
t = S
Short discrepancy time
t = 1 ... 255L1:
Discrepancy time in OB1 cycles
t = 1 ... 255L13:
Discrepancy time in OB13 cycles
Blocks and Their Functions
Explanation
9-33