S5-95F
Digital Output Module 4×DC 24/2 A
Source or Sink Output - Safety-Related -
0
1
2
3
DIGITAL OUTPUT
4 x 24V / 2A
6ES5 450-8FA11
1
2
3 4
9V
Control and test logic
5V
P
24V
M
5V
1
3
2
4
L+
M
L+
from other subunit;
sink output
EWA 4NEB 812 6210-02
M
P
L+ M
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
M
P
5
6
+9 V
GND
Data
V Ref
5
7
9
6
8
10
to other subunit;
source output
M
Technical Specifications
Number of outputs
Galvanic isolation
- in groups of
Load voltage L+
- rated value
- permissible range
Output current
for "1" signal
- rated value
- permissible range
- lamp load
max. 20 W
Residual current at
"0" signal
max. 1 mA
Short-circuit protection
- thermal
- electronic
Voltage induced on circuit
interruption (internal)
limited to
Switching frequency
- resistive load
max. 100 Hz
- inductive load (2 mH)
max. 2 Hz
Total permissible
current of outputs
Driving of digital input
Parallelling of outputs
Permissible ambient
temperature of PLC
- horizontal arrangement
- vertical arrangement
Length of cable
- unshielded
max. 200 m (660 ft.)
Insulation rating
Rated insulation voltage
(+9 V to L+)
- Insulation group
- tested with
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Current consumption
- from+9 V (CPU)
max. 60 mA
- from L+(without load)
max. 36 mA
Power loss
of the module
typ.
Weight
approx.
Module Spectrum
(6ES5 450-8FA11)
4
yes (transformer)
4
24 V DC
20 to 30 V
2 A at 40 °C/104 °F
1.5 A at 60 °C/140 °F
5 mA to 2 A
- 36 V
at 40 °C/104 °F: 8 A
at 60 °C/140 °F: 6 A
possible
possible, if outputs
decoupled by diodes
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
to VDE 0160
60 V AC
2×B
500 V AC
12 V AC
1×B
500 V AC
5 W
325 g (11.4 oz.)
A-5