Module Spectrum
Digital Input Module 8 x 5 to 24 V DC
.0
.1
.2
.3
.4
.5
.6
.7
1 -
2 -
DIGITAL INPUT
8 x 5 ... 24 V DC
6ES5 433-8MA11
1
2
3
4
S1
4.7 k
1
3
2
4
Optionally
to "S1"
X.1 X.0 X.3 X.2 X.5 X.4 X.7 X.6
A-12
L+
1
M
2
4
3
6
5
8
7
10
9
L+
M
8
5
6
+9 V
GND
Data
S2
5
7
9
6
8
10
Technical Specifications
Number of inputs
Galvanic isolation
- in groups of
Input voltage L+
- rated value
- "0" signal
- "1" signal
Permissible range
Input resistance
The LED displays
the evaluated signal
Inherent delay
approx.
Length of cable
- unshielded
max.
Rated insulation voltage
(+ 9 V to L+)
- insulation group
- tested with
Rated insulation voltage
(+ 9 V to
)
- insulation group
- tested with
Current consumption
- from + 9 V (CPU)
typ.
- from L+
typ.
Power loss of the
module
typ.
Weight
approx.
* reversible in groups of 8
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
tested with
not tested
Electromagnetic fields
to IEC 801-3
tested with
Fast transient burst
to IEC 801-4
tested with
S5-95F
(6ES5 433-8MA11)
8
yes (optocoupler)
8
5 to 24 V DC
V in approx. 25% L+
V in approx. 45% L+
4.5 to 30 V
4.7 k to L+ or M;
reversible on the back
of the module*
1 ms or 10 ms;
reversible on the back
of the module*
100 m (330 ft.)
30 V AC
2 x B
500 V AC
12 V AC
2 x B
500 V AC
6 mA
60 mA
2.4 W
225 g (8 oz.)
Severity rating 2
6 kV air discharge
Contact discharge
Severity rating 2
3 V / m
Severity rating 1
0.5 kV on supply lines
1 kV on signal lines
EWA 4NEB 812 6210-02