Siemens SIMATIC S5-95F Manual page 491

Table of Contents

Advertisement

Rules for Failsafe Operation of an S5-95F
Error Response from Slave Node
If a node fails to receive a valid frame within the stipulated SINEC L1 safety time for Receive,
The operating system sets bit 0 in the "Condition code and control byte for Receive" and clears
the Receive mailbox
The operating system flags an error in the SINEC L1 error word in system event data block
DB254
The operating system enters an error message in the error buffer in system event data block
DB254
The S5-95F responds as specified in DB1 (possible responses are a PLC STOP or the reaction
written in the user program)
18-40
S5-95F
EWA 4NEB 812 6210-02