SIMATIC S5
3964(R) Driver
1
System Configuration....................................................................................................... 3
2
External Device Selection ................................................................................................ 7
3
Communication Settings .................................................................................................. 8
4
Setup Items .................................................................................................................... 11
5
Cable Diagram ............................................................................................................... 15
6
Supported Device Addresses......................................................................................... 17
7
Device Code and Address Code.................................................................................... 18
8
Error Messages.............................................................................................................. 19
1
Siemens AG

Advertisement

loading

Summary of Contents for Siemens SIMATIC S5 Series

  • Page 1: Table Of Contents

    Siemens AG SIMATIC S5 3964(R) Driver System Configuration....................... 3 External Device Selection ....................7 Communication Settings ....................8 Setup Items ........................11 Cable Diagram ....................... 15 Supported Device Addresses..................17 Device Code and Address Code..................18 Error Messages......................19...
  • Page 2 SIMATIC S5 3964(R) Driver Introduction This manual describes how to connect the Display and the External Device (target PLC). In this manual, the connection procedure is described in the sections identified below: System Configuration "1 System Configuration" (page 3) This section lists the types of External Devices and SIO that you can connect.
  • Page 3: System Configuration

    SIMATIC S5 3964(R) Driver System Configuration The following section shows system configurations for connecting the Siemens AG External Device and the Display. Setting Cable Series Link I/F SIO Type Example Diagram CP521 SI RS-232C 100U Setting Cable SIMATIC 115U CP524...
  • Page 4 SIMATIC S5 3964(R) Driver IPC COM Port When connecting IPC with an External Device, the COM port used depends on the series and SIO type. Please refer to the IPC manual for details. Usable port Usable Port Series RS-232C RS-422/485(4 wire) RS-422/485(2 wire) COM1 , COM2,...
  • Page 5 SIMATIC S5 3964(R) Driver When setting up communication between an External Device and the RS-232C/422/485 interface module, use the IPC (RS-232C) or PS5000 (RS-422/485) cable diagrams. However, when using PFXZPBMPR42P2 in a RS-422/485 (4-wire) configuration with no flow control, connect 7.RTS+ and 8.CTS+, and connect 6.RTS- and 9.CTS-.
  • Page 6 SIMATIC S5 3964(R) Driver RS-422/485 (4 wire) DIP Switch Setting Description Reserved (always OFF) SIO type: RS-422/485 Output mode of SD (TXD) data: Always output Terminal resistance (220Ω) insertion to SD (TXD): None Terminal resistance (220Ω) insertion to RD (RXD): None Short-circuit of SDA (TXA) and RDA (RXA): Not available Short-circuit of SDB (TXB) and RDB (RXB): Not available RS (RTS) Auto control mode: Disabled...
  • Page 7: External Device Selection

    Enter an integer from 1 to 4 to define the number of Devices/PLCs to connect to the display. PLCs Manufacturer Select the manufacturer of the External Device to connect. Select "Siemens AG". Select the External Device model (series) and the connection method. Select "SIMATIC S5 3964(R)".
  • Page 8: Communication Settings

    SIMATIC S5 3964(R) Driver Communication Settings This section provides examples of communication settings recommended by Pro-face for the Display and the External Device. Setting Example 1 GP-Pro EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. GP-Pro EX Device/PLC Connection Manual...
  • Page 9 SIMATIC S5 3964(R) Driver External Device Settings Use the program controller (SIMATIC PG615) to configure communication settings for the External Device. Refer to your External Device manual for details. Set the RUN/STOP switch on the CPU unit to STOP. Turn the program controller power ON to check that it is configured as shown below. Setup Items Setting Value ON-LINE...
  • Page 10 SIMATIC S5 3964(R) Driver Press key 1 to display the first address [0000:KH=]. Set each address as shown below. To move the address, press the down key. Address Setting Value Address Setting Value 0000 0006 0009 0000 0001 0002 0007 0000 0002 0008...
  • Page 11: Setup Items

    SIMATIC S5 3964(R) Driver Setup Items Set up the Display’s communication settings in GP-Pro EX or in the Display’s offline mode. The setting of each parameter must match that of the External Device. "3 Communication Settings" (page 8) Setup Items in GP-Pro EX Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
  • Page 12 SIMATIC S5 3964(R) Driver Setup Items Setup Description Select the communication control method to prevent transmission and reception data Flow Control overflow. Enter the time (seconds) for which the Display waits for the response from the External Timeout Device, from "1 to 127". In case of no response from the External Device, use an integer from 0 to 255 to enter how Retry many times the Display retransmits the command.
  • Page 13 SIMATIC S5 3964(R) Driver Setup Items in Offline Mode • Refer to the Maintenance/Troubleshooting guide for information on how to enter offline mode or about the operation. Cf. Maintenance/Troubleshooting Guide "Offline Mode" • The number of the setup items to be displayed for 1 page in the offline mode depends on the Display in use.
  • Page 14 SIMATIC S5 3964(R) Driver Setup Items Setup Description Enter the time (seconds) for which the Display waits for the response from the External Timeout (s) Device, from "1 to 127" In case of no response from the External Device, use an integer from 0 to 255 to enter how Retry many times the Display retransmits the command.
  • Page 15: Cable Diagram

    SIMATIC S5 3964(R) Driver Cable Diagram The following cable diagram may be different from the cable diagram recommended by Siemens AG. Please be assured there is no operational problem in applying the cable diagram shown in this manual. • Please ground the FG pin of the External Device body. Use a grounding resistance of 100Ω 2mm or thicker wire, or your country's applicable standard.
  • Page 16 SIMATIC S5 3964(R) Driver Display side External Device side D-Sub 9pin (socket) D-Sub 25pin (plug) Shield Signal name Signal name RD(RXD) Display SD(TXD) RS(RTS) RS(RTS) CS(CTS) CS(CTS) Shell Display side External Device side Terminal Block D-Sub 25pin (plug) Shield Signal name Signal name RD(RXD) Display...
  • Page 17: Supported Device Addresses

    SIMATIC S5 3964(R) Driver Supported Device Addresses The following section shows the range of supported device addresses. Please note that the actual supported range of the devices vary depending on the External Device to be used. Please check the actual range in the manual of your External Device.
  • Page 18: Device Code And Address Code

    SIMATIC S5 3964(R) Driver Device Code and Address Code Use device code and address code if you select "Device Type & Address" for the address type in Data Displays. Device Code Device Device Name Address Code (HEX) Value of (Data Block (DB) No. × 0x10000) + Data Block 0000 Data Word (DW) No.
  • Page 19: Error Messages

    SIMATIC S5 3964(R) Driver Error Messages Error messages are displayed on the Display screen as follows: "No.: Device Name: Error Message (Error Occurrence Area)". Each description is shown below. Item Description Error number. Name of the External Device where an error has occurred. Device name is the title of the Device Name External Device set with GP-Pro EX.
  • Page 20 SIMATIC S5 3964(R) Driver GP-Pro EX Device/PLC Connection Manual...

This manual is also suitable for:

Simatic s5 3964(r)Simatic s5 3964