19 Operating variants of the parameters

The parameters stored in the burner control LMO39... can be displayed and changed
on the parameter level.
19.1
Parameters without index, with direct
display
19.1.1
Example of parameter 266 (preignition time) on the
parameter level
P
V
h min s
P
V
h min s
P
V
h min s
Basic Documentation LMO39...
19 Operating variants of the parameters:
Press button combination
000: Int.
With
, select the parameter group 100:
PArA.
With
, select the parameter group 200:
PArA.
Pressing the
parameter 226: Preignition time.
:
Press
Display: Parameter 266: flashes, value 3.675
does not.
/reset
Press
Display: 3.675
%
Press
preignition time to change mode one place to
the left.
Display: Preignition time 3.675 flashes.
%
Note!
To detect display errors, the value appears
one place shifted to the left.
Press
preignition time.
Display: Preignition time 3.822 flashes
%
VSD
F
A
button takes you to
/reset
to select preignition time.
or
to go to editing mode.
or
to shift the former
or
to select the required
:
to display
51/61