Siemens SIMATIC S5-95F Manual page 515

Table of Contents

Advertisement

Module Spectrum
Analog Input Module 4 x±10 V (continued)
Technical Specifications
Input ranges
(rated values)
Number of inputs
Galvanic isolation
Input resistance
Connection method
of sensors
Digital representation
of input signal
Measured value
representation
Measuring principle
Conversion principle
Integration time
(adjustable for optimum
noise suppression)
Encoding time
per input
- for 2048 units
- for 4095 units
Permissible voltage
difference
- between inputs
- between inputs and
central ground point
Permissible
input voltage
(destruction limit)
Fault indication for
- range exceeded
- sensor wire break
- general indication of
wire break
A-20
±10 V
1, 2 or 4
(selectable)
yes (inputs to
grounding point;
not between inputs)
50 k
two-wire
connection
12 bits+sign
(2048 units =rated
value)
two's complement
(left-justified)
integrating
voltage-time
conversion
(dual slope)
20 ms at 50 Hz
16.6 ms at 60 Hz
max.
60 ms at 50 Hz
max.
50 ms at 60 Hz
max.
80 ms at 50 Hz
max.
66.6 ms at 60 Hz
max.
±1 V
max.
75 V DC/60 V AC
max.
50 V DC
yes (more than
4095 units)
no
no
Noise suppression
for f=nx
(50/60 Hz±1%);
n=1,2, ...
- common-mode
min.
rejection (V
=1 V)
pp
- series-mode rejection
min.
(peak value of noise
< rated value of
input range)
Basic error limits
(operational error limits
at 25°C (77 °F), referred to the
input ranges of the module)
Operational error limits
(0 to 60 °C (32 to 140 °F),
referred to the input
ranges of the module)
Length of cable
- shielded
max.
Supply voltage L+
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(inputs to +9 V)
- insulation group
- tested with
Current consumption
- from +9 V (CPU)
typ.
Power loss of the
module
typ.
Weight
approx.
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
tested with
Electromagnetic fields
to IEC 801-3
tested with
Fast transient burst
to IEC 801-4
tested with
S5-95F
(6ES5 464-8MC11)
86 dB
40 dB
±0.2 %
±0.45 %
200 m (660 ft.)
none
12 V AC
1×B
500 V AC
60 V AC
1×B
500 V AC
70 mA
0.7 W
230 g (8 oz.)
Severity rating: none
4 kV air discharge
<2 kV contact
discharge
Severity rating 2
3 V / m
Severity rating 3
1 kV on signal lines
EWA 4NEB 812 6210-02

Advertisement

Table of Contents
loading

Table of Contents