Siemens SIMATIC S5-95F Manual page 367

Table of Contents

Advertisement

S5-95F
Example: The S5-95F is to be a slave station and have the slave number 2 on the SINEC L1 bus.
Subunit A is interfaced to the L1 bus.
The following conditions apply to data transfer:
Coordination byte UVB is flag byte 10
Data is to be transmitted over data path 1 to slave 13 and 14
Data is to be received over data paths 1 and 2 from slaves 13 and 14
Slave 13 is an S5-115F programmable controller with CPU 942-7UF15 and slave 14 is an
S5-95F programmable controller
The SINEC L1 safety time is 3 seconds for all connections
If no valid frame can be received within the safety time, the S5-95F goes to STOP
Table 13-5. Initializing the Interface for Failsafe Data Interchange
Parameter in
the Default
DB
Block ID "SINEC L1"
SL1:
PG bus number
PGN N
(required for executing
programmer functions over the
L1 bus; default value is NO)
Slave number
SLN N
Default value is NO
Block ID: "SINEC L1 failsafe"
SL1S:
User Valid Byte
UVB N
Data path 1 (send) is physically
D1S N
interfaced to subunit ...; default
value is NO.
Data path 1 (receive) is physically
D1E N
interfaced to subunit ...; default
value is NO.
Data path 2 (send) is physically
D2S N
interfaced to subunit ...; default
value is NO.
Data path 2 (receive) is physically
D2E N
interfaced to subunit ...; default
value is NO.
EWA 4NEB 812 6210-02
Description
S5-95F on SINEC L1
Value for the
Permissible Values
Example
PGN 1
SLN 2
UVB MB 10
D1S A
k={N, A, B, H} where
H ˆ =subunits A and B
D1E A
D2S A
D2E A
PGN x
(x=1 to 30)
SLN x
(x=1 to 30)
FY x
(x=0 to 255)
D1S k
N ˆ =no
A ˆ =subunit A
B ˆ =subunit B
(high-availability
SINEC L1 bus)
D1E k
D2S k
D2E k
13-13