Intrusion Walk Test; Service Walk Test - Bosch B9512G-E Installation Manual

Table of Contents

Advertisement

Control Panels
Doing a fire walk test
1.
2.
3.
4.
5.
Notice!
Multiple detectors
If the point loop has multiple detectors, then the keypad emits a tone as confirmation for
each fault detected.
16.2.2

Intrusion walk test

An intrusion walk test includes points meeting the following criteria:
A controlled point can be programmed for trouble when disarmed.
Performing an intrusion walk test
1.
2.
3.
4.
5.
16.2.3

Service walk test

A service walk test allows you to walk test points assigned to any point type. The area scope
of the keypad that initiates the walk test determines which points are included in the test. All
points are included when the keypad scope is panel wide, including those with a Point Profile
of 0.
A service walk test includes points:
During a service walk test:
Performing a service walk test
1.
Bosch Security Systems, Inc.
Choose a keypad to conduct the test. Make sure that all areas are off (disarmed).
Open Main Menu and then go to the [3] Actions Menu > [3] Test > [1] Walk Test > [1]
Fire.
The keypad shows the number of points that remain untested.
To view the list of points, press Enter or View untested points. To scroll through the list
of points, use
/Previous or
When you fault a point (press the test button on a smoke detector for example), the
keypad emits a brief tone and shows the point name.
Have a point source other than Unassigned
Have a point profile not set to Disabled (must be non-zero)
Point type must be for a Controlled Point; Part-On, Interior, or Interior Follower
Are not service bypassed
Are not invisible points
Choose a keypad to conduct the test. Make sure that all areas are off (disarmed).
Open Main Menu and then go to the [3] Actions Menu > [3] Test > [1] Walk Test > [1]
Intrusion.
The keypad shows the number of points that remain untested.
To view the list of points, press Enter or View untested points. To scroll through the list
of points, use
/Previous or
When you fault a point (open a door for example), the keypad emits a brief tone and
shows the point name and that it has been tested (for example, Pt-4: P4 Follow Tested).
with a point source other than Unassigned
that are disabled (Point Profile set to 0) in addition to those that are enabled (non-zero
Point Profile)
that you have service bypassed
The summary alarm and summary fire remain off, because there are no Fire or Burg alarm
conditions to summarize.
The test does not generate any Extra Point troubles.
The test does not log any Extra Point events.
Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
/Next.
/Next.
Installation Manual
Program and test the control panel | en
2018.07 | 10 | F.01U.303.996
93