Control Panel
15.2.2

Intrusion walk test

An intrusion walk test includes points meeting the following criteria:
A controlled point can be programmed for trouble when disarmed.
Performing an intrusion walk test:
1.
2.
3.
4.
5.
15.2.3

Service walk test

A service walk test allows you to walk test points assigned to any point type. The area scope
of the keypad that initiates the walk test determines which points are included in the test. All
points are included when the keypad scope is panel wide, including those with a Point Index
of 0.
A service walk test includes points:
During a service walk test:
Performing a service walk test:
1.
2.
3.
4.
5.
Bosch Security Systems, Inc.
Have a point source other than Unassigned
Have a point index not set to Disabled (must be non-zero)
Point type must be for a Controlled Point; Part-On, Interior, or Interior Follower
Are not service bypassed
Are not invisible points
Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
Open the Main menu and then go to the [3] Actions menu > [3] Test > [1] Walk Test > [2]
Intrusion option.
The keypad shows the number of points that remain untested.
To view the list of points, press [ENTER] or [View untested points]. To scroll through the
list of points, use
/[PREV] or
When you fault a point (open a door for example), the keypad emits a brief tone and
shows the point name and that is has been tested (for example, Pt-4: P4 Follow Tested).
with a point source other than Unassigned
that are disabled (Point Index set to 0) in addition to those that are enabled (non-zero
Point Index)
that you have service bypassed
The summary alarm and summary fire remain off, because there are no Fire or Burg alarm
conditions to summarize.
The test does not generate any Extra Point troubles.
The test does not log any Extra Point events.
Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
Open the Main menu and then go to the [3] Actions > [3] Test > [1] Walk Test > [3]
Service option.
Enter your passcode and press [ENTER]. The keypad shows the number of points that
remain to be tested.
To view the list of points, press [ENTER] or [View untested points]. To scroll through the
list of points, use
/[PREV] or
When you fault a point (move in front of a motion sensor for example), the keypad emits a
brief tone and shows the point name and information (for example, Area-1 Point-7
Onboard: Short).
Installation and System Reference Guide
Program and test the control panel | en
/[NEXT].
/[NEXT].
75