Bosch B9512G-E Installation Manual page 120

Table of Contents

Advertisement

120 en | Approved applications
Product feature/option
Bat Fail/Restoral Report
Area 1 Area On
A# Delay Restoral
Restart Time
Area # Fire Time
Supervised (within the Keypads
section)
Trouble Tone (within the Keypads
section
Remote Program
A# Fire Bell
A# Reset Sensors
U### Area # Auth
U### Passcode
P## Silent Bell
P## Invisible Point
P## Local While Disarmed
P## Local While Armed
P## Disable Restorals
P## Bypassable
P## Swinger Bypass
P## Resettable
Sked## Function
Sked## Defer Test
Sked## Hourly Test (Report?)
Sked## Time
Sked## Date
Sked## Sunday
Sked## Monday
Sked## Tuesday
2018.07 | 10 | F.01U.303.996
Permitted in UL 864?
(Yes/No)
Yes
Required to send
system status reports
Yes
Yes
Yes
Yes
Yes
Disable / Enable
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Yes
Required
No
No
Enter valid time
No
Yes
Yes
Yes
Installation Manual
Possible settings
Yes / No
Yes / No
Yes / No
5 to 55 seconds
1 to 90 min
Yes / No
Yes / No
-, E, or P
0 to 599
0 to 599
0 to 13
3-, 4-, 5-, or 6-digit
passcode
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Varies
Yes / No
Yes / No
00:00 to 23:59
mm/dd
Yes / No
Yes / No
Yes / No
Control Panels
Settings permitted in
UL 864
Set to Yes
Set to Yes
Set to Yes
5 seconds
5 min (check with AHJ)
Set to Yes
Set to Yes
Set to P
Program with a relay
Program with a relay
Program an Authority Level
for the Fire Area
Must program at least one
passcode. Passcode must
have at least 4 digits.
Set to No
Set to No
Set to No
Set to No
Set to No
Set to No
Set to No
As required
Sked Function Send Test
Report
Set to No
Set to No
00:00 to 23:59
Set to No
Set to Yes
Set to Yes
Set to Yes
Bosch Security Systems, Inc.