Control Panel Board Overview - Bosch B9512G-E Installation Manual

Table of Contents

Advertisement

Control Panels
17

Control panel board overview

BATTERY STATUS
Off: Normal
On: Missing
Quick Flash: Low
Slow Flash:
Charging
Minimum system requirements for Classification in accordance with ANSI/SIA
Low 12.1 VDC
CP-01-2010. UL Listed and Classified control unit Model B9512G and B8512G.
Do not connect
Load Shed 10.2 VDC
UL Listed and Classified keypad Model B942, B930, B925F, B926F, B921C,
to a receptacle
B920, B915, D1255RB, D1256RB and D1257RB. UL Listed Local Bell.
controlled by
a switch.
The equipment should be installed in accordance with the NFPA 70 (National Electrical
Code) and NFPA 72 (National Fire Alarm Code).
CLASS 2
1
Depending on the application, the installation may need to be in accordance with one or
more of the following UL standards: UL681, UL1076, UL1641 and C22.1, CEC, Part 1.
16.5 VAC 40 VA 60 Hz
Use of a D185 is not suitable for remote station protected premises service where separate
2
TRANSFORMER
transmissions circuits are required for fire, supervisory (when applicable) and trouble
signals.
All external connections except Terminal 5 (BATTERY(+) are inherently power limited.
3
+ AUX POWER
Requirements for battery standby time might reduce allowable output.
POWER SUPPLY REQUIREMENTS
-
4
BATTERY (
)
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all Accessory Devices. For System Loading,
refer to the B9512G/B8512G UL Listing Document, ULLD. Auxiliary powered devices: 11.8 to 12.5 VDC
Battery: Replace every 3 to
5
BATTERY ( + )
5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
OUTPUT
6
A (1)
The system is intended to be checked by a Qualified Technician at least every 3 years. The types of initiating circuits the control
panel has been approved for are A, M, WF, SS. The types of signaling the control panel has been approved for are DAC, OT, NC,
OUTPUT
RevPol.
7
B (2)
WARNING!
To prevent risk of shock,
OUTPUT
8
disconnect AC power and
C (3)
communication lines before
servicing.
9
COMMON
EARTH GROUND
10
WARNING!
WARNING!
Multi-Battery
Incorrect wiring will
installation requires
damage this
Model D122 or D122L
equipment.
Dual Battery Harness.
Devices powered by
Improper installation
any output must be
can be a fire hazard .
supervised.
USB POWER
STATUS
L
I
N
K
USB
ETHERNET
Callout ᅳ Description
1 ᅳ BATTERY STATUS LED
2 ᅳ Holes to stabilize plug-in modules
3 ᅳ Plug-in module connectors
4 ᅳ Plug-in module retention clips
5 ᅳ SDI2 wiring
6 ᅳ SDIx wiring (use as SDI or SDI2)
7 ᅳ Heartbeat LED (blue)
8 ᅳ RESET button
9 ᅳ Tamper switch connector location
10 ᅳ Zonex module connector location
11 ᅳ Sensor loop terminals for points 1 to 8
Bosch Security Systems, Inc.
The B9512G/B8512G Control Panel is UL Listed For CS, RS, L, AUX, Prop and Res Fire and Res, Prop,
Cent. Stat, Local, and PS Con. Merc. Burg, MSV, BSV, Holdup, suitable as a dual line trans. sys.
Signaling means: DAC, Cell or IP
Refer to the system wiring diagrams in the B9512G/B8512G
ULLD and to the D125B Installation Instructions for compatible
smoke detectors. 2-wire Compatible Identifier "A". Printed
information describing proper installation, operation, testing,
maintenance, repair service and response to an alarm is to be
provided with this equipment.
ON-BOARD POINTS
WARNING!
Owner Instructions (P/N F.01U.307.371): Not to
be removed by anyone except occupant.
Voltage Ranges: Open 3.7 - 5.0 VDC, Short 0.0 - 1.3 VDC, Normal 2.0 - 3.0 VDC
1 k
End-of-line-Resistors Required (P/N 15093130-004), Max Loop Current: 5 mA
Point 3
Point 4
Point 1
Point 2
11
12
13
14
15
16
B
A
S
E
T
POINT 1 COM POINT 2 POINT 3 COM POINT 4
For more information, refer to:
Battery discharge and recharge schedule, page 39
Installation and module wiring (B430), page 44 or
Installation and module wiring (B44x)
SDI2 devices general system wiring, page 102
SDI2 devices general system wiring, page 102 or SDI and
ZONEX wiring, page 100
Installer keypads and SERVICE MODE, page 123
Installing the enclosure, page 31
SDI and ZONEX wiring, page 100
On-board points, page 72
Installation Manual
Point 5 Point 6
Point 7 Point 8
17
18
19
20
21
22
POINT 5 COM POINT 6 POINT 7 COM POINT 8
Control panel board overview | en
MOD-2
MODULE RELEASE
MOD-1
PWR+/R
30
29
A/Y
28
B/G
COM/B
27
PWR+/R
26
A/Y
25
B/G
24
COM/B
23
ZONEX
TMPR
RESET
ZONEX
TMPR
2018.07 | 10 | F.01U.303.996