en | Power supply
6.2.1

SDI2 address settings

Notice!
The module reads the address switch setting only during module power up. If you change the
setting after you apply power to the module, you must cycle the power to the module in order
for the new setting to take effect.
If multiple B520 modules reside on the same system, each B520 module must have a unique
address.
6.2.2

Supervision

The control panel supervises any B520 on the SDI2 bus.
With any failure to receive an expected response from a B520, all keypads show a system
fault. The control panel sends a module trouble report to the central station (if configured for
module trouble reports).
6.2.3

Auxiliary power supply trouble conditions

Each auxiliary power supply module on the SDI2 bus monitors several conditions including AC
status, battery status, over current status, and a tamper input. Each of these conditions
produces a unique system trouble condition at all keypads. The control panel sends a module
trouble report to the central station (if configured for module trouble reports).
6.2.4

Installation and control panel wiring (B520)

Calculate power consumption
Make sure that there is enough power for the module and the other powered devices that you
want to connect to the system.
Refer to On-board outputs, page 65.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
Installing the module
1.
2.
3.
4.
Wiring to earth ground
4
Notice!
Earth ground reference
Do not use telephone or electrical ground for the earth ground connection. Use 14 AWG (1.8
mm) to 16 AWG (1.5 mm) wire when making the connection
Use a grounding rod or a cold water pipe.
Run wire as close as possible to grounding device.
2018.07 | 10 | F.01U.303.996
Set the module address.
Insert the plastic mounting clips onto the standoff locations inside the enclosure or on a
mounting skirt, when required.
Mount the module onto the plastic mounting clips.
Tighten the supplied mounting screws.
To help prevent damage from electrostatic charges or other transient electrical surges,
connect the system to earth ground before making other connections.