en | On-board outputs
30
Powers serial device interface 2 (SDI2) devices, such as keypads and expansion modules.
Powers ZONEX modules such as the D8125, D8128D, and D8129 connected through the B600.
10.3

Continuous power outputs

3 26 30
The continuous current draw for powered devices connected to Terminals 3, 26, and 30, and
the ZONEX connector must not exceed 1.4 A. Devices powered from these outputs operate at
12.0 VDC Nominal.
Notice!
Power Restricted for Fire and Combined Fire and Burglary Systems
Use the Fire system power formula, page 67 to calculate the current available for fire and
combined fire and burglary systems
10.4

Programmable power outputs

6
The power outputs at Terminals 6, 7, and 8 are programmed as Outputs A (1), B (2), and C
(3).
Assign each output an output type (Steady Alarm Bell, for example), when assigning it to an
area. You can assign an output to one or more areas.
The defaults are:
The Program Entry Guide contains complete instructions for programming outputs. Refer to
the Bell Parameters section of the program to set the Fire Bell, Alarm Bell output responses
for outputs. Four annunciation patterns are available: Steady, Pulsed, California Standard, and
Temporal Code 3.
If Terminals 6, 7, and 8 do not provide the expected output, check:
10.4.1

Terminals 6 and 7

6
When activated, Terminals 6 (Output A) and 7 (Output B), provide a positive (+) 12.0 VDC
Nominal power output. Use the power at Terminals 6 and 7 to power bells, siren drivers,
piezoelectric sounders, electronic horns, or other devices.
Programming determines the format of the output and the conditions that activate it.
2018.07 | 10 | F.01U.303.996
SDI2 Power+ / R
ZONEX Power
7
8
Output A (1) - Terminal 6 - as a Steady Alarm Bell output
Output B (2) - Terminal 7 - as a Pulsed Fire Bell output
Output C (3) - Terminal 8 - as a Verification or Reset output for smoke detectors
The Outputs section of the program for Outputs A (1), B (2), and C (3).
The Bell Parameters section of the program to confirm that the Alarm and Fire Bell
responses are programmed for the expected duration and pattern.
The Point Assignments section to confirm that each point is programmed for the expected
local response.
7
Installation Manual
Control Panels
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B9512gB8512g-eB8512g

Table of Contents