Uni t Fa u lts
(Continued)
The Thermolator has detected a problem with the internal components, wiring, electrical power, or operat-
ing environment. Without correction, the fault could lead to equipment damage or personal injury if it is
not corrected.
•
The controller displays an error code indicating the cause of the problem.
•
The TCU may take automatic control actions, based on the nature of the fault, to best protect the op-
erator and the TCU until the fault is corrected.
•
If the optional alarm package is installed, the fault strobe will illuminate and the audible alarm will
activate.
•
Some faults require a power cycle to reset.
Fault
Prr
E
Return Probe Fault Low
The "To Process" RTD is mal-
functioning or has a short circuit.
WARNING: Only qualified elec-
trical service personnel should
examine and correct problems
that require opening the unit's
electrical enclosure or checking
electrical current.
u ALARM LED flashes in
conjunction with RETURN
LED.
u Optional strobe, sounder,
dry contacts actuated.
u Pump turns off.
u Heater turns off.
u Cooling valve closes.
This fault will automatically
reset when the problem is cor-
rected.
Possible Cause
Do you have a break in your RTD
wiring?
Has the RTD itself failed or sus-
tained physical damage?
Solution
Check the RTD loop wiring with a
VOM.
See Checking the RTD.
Test the RTD with a VOM.
See
Checking the RTD.
If damaged, replace the RTD.
Tro ub l es hoo ti n g
I
6-25