Mo db u s O p ti on Pa r am e te rs
Register
Command
8018
Supply Temperature Retransmit Range Low (°C)
8020
Supply Temperature Retransmit Range High (°C)
8022
Low Temperature Safety – User Set (°C)
8024
High Temperature Safety – User Set (°C)
8026
Proportional Band (°C)
8052
Pump Running Hours
8054
Setpoint Temperature (°C)
8056
Low Temperature Safety – Factory Set (°C)
8058
High Temperature Safety – Factory Set (°C)
8070
Supply Temperature Input Offset
8072
Return Temperature Input Offset
8074
Remote Setpoint Temperature Input Offset
8080
Remote Setpoint Limit Temperature (°C)
8082
Remote Setpoint High Temperature Limit (°C)
M od bu s Re gi s t e r s
The following is a list of Modbus Registers that are remotely available.
Notes:
There is a limitation on the maximum Modbus block size of 40 for integers and 20
for floats.
Additional settings include:
Baud: Set by parameter bU, 9600 baud by default.
Parity: None
Data bits: 8
Stop bits: 1
Flow control: None
It is common for external software to apply an address offset of "1", so you may need
to add "1" to the Modbus addresses based on the software in the remote system.
In newer versions of Modbus, you may have to append a "4" or a "40" prefix on the
registers listed.
For example, to get to "MACHINE STATE" in register 4002, you may have to access
register 4002, 4003, 44002, 44003, 404002, or 404003. Once you test your system and
get a valid response, you will know the rules to consistently apply to your system for all
addresses.
(Continued)
Poll
Select
Description
R
Floating Point
R
Floating Point
R/W
Floating Point
R/W
Floating Point
R/W
Floating Point
R
Floating Point
R/W
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
O per a t i on
I
4-19