Access to the program menu is password protected to prevent unintended alteration to the
program settings and parameters. To access the programming menu the unit must be in a
stopped state.
To enter the program menu stop the unit then press and hold the Display/Program
button for 10 continuous seconds to put the controller in program mode. The Program
Mode light flashes yellow and the display will show PAS on the Process display and 000
on the Set Point display. The unit is now ready to have the password entered. From the
factory, the password is set to 000.
5
Use the Up or Down arrow buttons to increase the numeric value on the Set
Point display until the correct password value is shown.
6
To enter the password, press and release the Start button. If an incorrect password
is entered the Set Point display shows no and the Process display shows PAS. After
5 seconds, the unit will go back to the password entry mode and display PAS on the
Process display and "blanks" on the Set Point display. If no activity occurs for another
5 seconds, the controller exits the programming mode and returns to the Stopped
state.
7
Once in the program menu, use the Display/Program button to scroll through
the different adjustable parameters
8
To change an item, press the Display/Program button until the item code dis-
plays in the Process display. Pressing the Alarm Reset button and Display/Program
button at the same time will reverse the direction the Display/Program button indexes
through the menu items.
9
Once the desired menu item code displays in the Process display, use the Up and
Down arrow buttons to adjust the value shown in the Set Point display until the de-
sired value is shown. Press the Start button to enter the display value. Press the Stop
button to cancel and revert to the previously value.
10
There is a Master Reset function to restore all User menu parameters to their factory
default values. To initiate a Master Reset the unit must be in a stopped state. Once
the unit is stopped, press and hold the Alarm Silence/Reset button and Stop button
simultaneously for 10 consecutive seconds until PRG is displayed on the Set Point
display and RSt is displayed on the Process display. To confirm a Master Reset is
desired, press and release the Start button and the system will perform a Master Reset
and reboot. The Master Reset is aborted after the PRG is displayed on the Set Point
display and RSt is displayed on the Process display by turning the control power off
or taking no action for 10 consecutive seconds.
(see Program Menu Items table).