GE PACSystems RX7i Reference Manual page 113

Cpu
Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

Chapter 2. CPU Features & Specifications
The CPE100/CPE115 are programmed and configured over Ethernet via GE's Proficy* Machine Edition
(PME) software. Each is a standalone CPU with the following features:
A built-in PACSystems RSTi-EP PLC CPU
o User may program in Ladder Diagram, Structured Text, Function Block Diagram.
o Both CPE100 & CPE115 have configurable data and program memory. This entire memory will
be preserved between power cycles.
o Supports auto-located Symbolic Variables that can use any amount of user memory.
o Reference table sizes include 2k bits for discrete %I and %Q and up to 2k words each for analog
%AI and %AQ. Bulk memory (%W) also supported for data exchanges.
o Supports up to 512 program blocks. Maximum block size is 128KB.
Supports two independent 10/100 Ethernet LANs. LAN1 has only one port and is dedicated to high
speed Ethernet and whereas LAN2 is comprised of three switched ports (labelled as 2, 3 & 4)
configurable either as a second embedded Ethernet controller or an embedded PROFINET controller.
All four ports are located on the front panel, as shown in Figure 31.
The embedded communications interface has dedicated processing capability, which permits the
CPU to independently support LAN1 and LAN2 with:
o up to 16 combined SRTP Server and Modbus TCP Server connections out of which:
a) Modbus TCP cannot exceed more than 8 simultaneous connections.
b) SRTP server cannot exceed more than 16 simultaneous connections.
o 8 Clients are permitted; each may be SRTP or Modbus TCP or a Combination of both.
o up to 8 simultaneous Class 1 Ethernet Global Data (EGD) exchanges.
The PLC may use one, two or three of the Ethernet ports of LAN2 to support the embedded Simplex
PROFINET I/O Controller. PROFINET supports up to 8 I/O devices with update rates of 16 – 512ms. It
is not recommended to use update rates below 16ms.
The CPE100/CPE115 is secure by design, incorporating technologies such as secure boot, trusted
platform module (disabled), and encrypted firmware updates.
Module LEDs on the face plate provides basic status and control information of CPE100/CPE115.
Ability to display serial number and date code in PME Device Information Details.
Media Redundancy Protocol (MRP) allows the CPE100/CPE115 to participate in a PROFINET I/O
network with MRP ring technology. This eliminates the I/O network as a single point of failure. The
CPE100/CPE115 may be used as either a Media Redundancy Manager or Media Redundancy Client.
OPC UA Server supports up to 2 concurrent sessions with up to 4 concurrent variable subscriptions
and up to 1000 variables.
Modbus RTU Slave support on two serial ports i.e. RS-232 and RS-485 with both 2-wire and 4 -wire
interface. These ports are located on the underside side of the controller and does not provide any
type of isolation.
Operating temperature range -40C to 70C (-40F to 158F).
The CPE100/CPE115, when shipped, is configured only for DIN-rail mount. An alternate panel-mount
adaptor plate (ICMFAACC001-AA) is optional and not included in the ship-set.
102
PACSystems* RX7i, RX3i and RSTi-EP CPU Reference Manual
GFK-2222AD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pacsystems rsti-epPacsystems rx3i

Table of Contents