PROFINET Controller (PNC001) and PROFINET I/O Sweep Impact
The PLC CPU sweep impact for a PROFINET IO network is a function of the number of PNCs, the number
of PROFINET devices, and the number of each PROFINET device's IO modules. The table below shows the
measured sweep impact of the RX3i PROFINET Controller, supported VersaMax PROFINET devices, and
I/O modules.
Sweep Impact Item
RX3i PROFINET Controller
(PNC)
RX3i Devices
PROFINET Scanner
(PNS) IC695PNS001
ALG442 Mixed Analog
ALG220 Analog Input
ALG390 Analog
Output
MDL645 Discrete
Input
MDL740 Discrete
Output
VersaMax Devices
PROFINET Scanner
(PNS), IC200PNS001
Discrete Input Module
(8/16/32 pt.)
Discrete Output
Module (8/16/32 pt.)
Analog Input Module
(15 channel)
Analog Output Module
(12 channel)
CMM020 (64AI/64AQ)
To calculate the total expected PLC sweep impact for a PROFINET I/O network, add the individual sweep
impact times for each PROFINET Controller, PROFINET Device, and PROFINET Device I/O module, using
the times provided above.
For example, for a PROFINET I/O network that consists of one PNC and one VersaMax PROFINET Scanner,
which has both an 8-point input and an 8-point output module:
Expected PLC Sweep Impact = 50 (PNC) + 40 (PNS) + 23 (8pt. Input) + 18 (8pt. Output)
GFK-2222AD
CPU315/CPU320
CPE302/CPE305/CPE310
(µs)
50
46
54
27
24
23
22
40
23
18
59
21
204
=131 µs.
April 2018
Appendix A. Performance Data
CPE330
w/PNC001
(µs)
(µs)
48
43
73
42
76
38
45
29
33
12
36
18
31
9
80
38
40
23
45
24
96
67
45
27
263
188
CPE330
CPE400
w/Embedded
w/Embedded
PNC
PNC
(µs)
(µs)
16
12
10
24
25
20
14
10
13
10
15
10
14
9
15
24
10
10
13
12
10
11
12
14
18
18
295