GE PACSystems RX7i Reference Manual page 123

Cpu
Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

Chapter 3. CPU Configuration
Settings Parameters
RUN/STOP
Enables or disables the physical operation of the RUN/STOP Switch.
Switch
Choices:
Enabled: Enables you to use the physical switch on the PLC to switch the PLC into STOP
Mode or from STOP Mode into RUN Mode and clear non-fatal faults.
Disabled: Disables the physical RUN/STOP Switch on the PLC.
Default: Enabled.
Note:
Memory
Enables or disables the Memory Protect feature associated with the RUN/STOP Switch.
Protection
Choices:
Switch
Enabled: Memory Protect is enabled, which prevents writing to program memory and
configuration and forcing or overriding discrete data.
Disabled: Memory Protect is disabled.
Default: Disabled.
Power-up
Selects the CPU mode to be in effect immediately after power-up.
Mode
Choices: Last, Stop, Run.
Default: Last (the mode it was in when it last powered down).
Note:
Modbus
Specifies the type of memory mapping to be used for data transfer between Modbus TCP/IP
Address Space
clients and the PACSystems controller.
Mapping Type
Choices:
Disabled: The Disabled setting is intended for use in systems containing Ethernet firmware
that does not support Modbus TCP.
Standard Modbus Addressing: Causes the Ethernet firmware to use the standard map,
which is displayed on the Modbus TCP Address Map tab.
Default: Disabled
For details on the PACSystems implementation of Modbus/TCP server, refer to PACSystems
RX7i & RX3i TCP/IP Ethernet Communications User Manual, GFK-2224.
Universal Serial
RX3i CPE302/CPE305/CPE310/CPE330/CPE400 CPUs only. Enables or disables the USB
Bus
port for use with RDSD (Removable Data Storage Devices). The USB port is enabled by
default in the CPE302/CPE305/CPE310/CPE330 and in the hardware configuration.
If a CPU310 configuration is stored to a CPE310, the USB port will be enabled.
112
If COM1 and COM2 are configured for any protocol other than RTU Slave or SNP
Slave, the RUN/STOP Switch should not be disabled without first must making sure
that there is a way to stop the CPU, or take control of the CPU through another
device such as an Ethernet interface. If the CPU can be set to STOP Mode, it will
switch the protocol from Serial I/O to the STOP Mode protocol (default is RTU Slave).
For details on STOP Mode settings, refer to COM1 and COM2 Parameters.
This applies to COM1 on the CPE302/CPE305, which has only one serial port.
This note does not apply to CPUs which have no serial ports.
If the battery or Energy Pack is missing or has failed and if Logic/Configuration
Power-up Source is set to Always RAM, the CPU powers up in STOP Mode
regardless of the setting of the Power-up Mode parameter.
PACSystems* RX7i, RX3i and RSTi-EP CPU Reference Manual
GFK-2222AD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pacsystems rsti-epPacsystems rx3i