Advertisement

5.2.

Load output

Output
Steady-state voltage variation
Rated frequency
Frequency accuracy
Load power factor range
Maximum fault clearing current
Independent mode
Power conditioning mode
Overload power ratings
Power conditioning mode
Independent mode
Power Distribution system
Voltage distortion THDv
Table 5.3: HiPerGuard MV UPS output specifications
5.3.

Energy Storage

Energy Storage
Type
Supplier
Autonomy range
Voltage Range
Inverter fast charging power
Auxiliary charger
Table 5.4: Energy Storage specifications
HI PE RG UA RD M V UP S U S E R M A N UA L
±1%
50 Hz or 60 Hz
± 0.1%
0.9 leading to 0.8 lagging
360%, 2 s
460%, 2 s
110%, 5 min
135%, 1 min
125%, 30 s
IT, 3-Wire Output
< 2.5%
Li-Ion batteries (not in the
scope of UPS supplier)
ABB qualified
15 sec to 15 min
520 Vdc to 750 Vdc
Typically 250 kW
Yes, 3kW
TE C H NI C A L S PE C I FI CAT IO NS
Applicable to independent mode only
Nominal power factor 1.0
From nominal conditions
Battery sizing dependent
Please contact ABB for other
distribution systems
Full linear load, under nominal
conditions, operating on power
conditioning mode
45/103