X2A Input State - KEB COMBIVERT F5 Instruction Manual

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

X2A Input State

Displayed
Value
0
1
2
4
5
8
9
16
17
32
33
64
65
128
129
Diagnostic Parameters
Terminal X2A
This parameter displays the status of the digital inputs on terminal X2A.
Each input has a specific value. See the table below for decoding.
Terminal
number(s)
Description
All X2
No signals are active on terminal X2A.10 to X2A.17
X2A.16
Only the enable signal is active on X2A.16. Drive will not run
until one of the direction signals on X2A.14 or X2A.15 are
active
X2A.17
Only the fault reset signal is active on X2A.17
X2A.14
Only the up signal is active on X2A.14. Drive will not run until
enable signal on X2A.16 is active.
X2A.16,X2A.14
Both the enable and up signals are active. This is normal
during operation.
X2A.15
Only the down signal is active on X2.4. Drive will not run until
enable signal on X2.1 is active.
X2A.16,X2A.15
The enable and down signals are active. This is normal during
operation.
X2A.10
Only the Leveling speed signal at X2A.10 is active. Drive will
not run unit enable signal on X2A.16 and direction signal on
X2A.14 or X2A.15 are active.
X2A.10,X2A.16
Both the enable and Leveling speed signals are active. A
direction signal is required to allow operation.
X2A.11
Only the HighLeveling speed signal at X2A.11 is active. Drive
will not run unit enable signal on X2A.16 and direction signal on
X2A.14 or X2A.15 are active.
X2A.11,X2A.16
Both the enable and HighLeveling speed signals are active. A
direction signal is required to allow operation.
X2A.12
Only the High speed signal at X2A.12 is active. Drive will not
run unit enable signal on X2A.16 and direction signal on X2A.14
or X2A.15 are active.
X2A.12,X2A.16
Both the enable and High speed signals are active. A direction
signal is required to allow operation.
X2A.13
Only the Inspection speed signal at X2A.13 is active. Drive
will not run unit enable signal on X2A.16 and direction signal on
X2A.14 or X2A.15 are active.
X2A.13,X2A.16
Both the enable and Inspection speed signals are active. A
direction signal is required to allow operation.