Parameter Description - Motor Data

Rated Motor Speed

Rated Motor Current

Rated Motor Frequency

Rated Motor Voltage

64
Unit:
PM
Value range :
Factory setting:
Adjustment value:
For permanent magnet synchronous motors there is no slip.
Therefore the value entered must be exactly the value on the
name plate of the motor. With this there is no further adjustment
necessary.
Enter the motor nameplate rated current (FLA).
IM
Unit:
Value range:
PM
Factory setting:
Adjustment value:
Enter the exact rated frequency of the motor.
IM
Unit:
Value range:
PM
Factory setting :
Adjustment value:
Enter the name plate rated voltage.
IM
Unit:
Value range:
Factory setting:
Adjustment value:
Enter the no load phase to phase back EMF rms voltage at
PM
1000 rpm.
Unit:
Value range:
Factory setting :
Adjustment value:
Note: this value is typically over 1000V as it is the voltage
value at 1000 rpm not at the rated speed value.
rpm
10.0....6000.0 or 500.0
(based on config mode)
1165.0 or 150.0
(based on config mode)
in accordance with the motor name plate
ampere
1.0...1.1 x Inverter rated current
8.0 A
in accordance with the motor name plate
hertz
4.0...100.0 Hz
60.0 Hz
in accordance with the motor name plate
volt
120...500 V
230 or 460 V based on drive voltage
in accordance with the motor name plate
Vrms / 1000 rpm
1...32000 V/krpm
230 or 460 V based on drive voltage
in accordance with the motor name plate