Parameter Description - Basic Set Up

6.2 LF-Elevator Parameters

Signal Operating Mode

56
This value determines the type of speed selection and rotation setting.
Value range:
d SPd
A tor
A SPd
SErSP
Factory setting:
d SPd
Value
Control mode
Digital Speed Control
d SPd
terminals X2A.10, X2A.11,
X2A.12,X2A.13
Analog Torque Control
A tor
-10V...0... +10V terminals
X2A.1, X2A2, X2A.3, X2A4
Analog Speed Control
A SPd
-10V...0...+10V terminals
X2A.1, X2A2
Digital Serial Speed Control
SErSP
Serial communication
16 bit signed speed value
When LF.2 = 3 then: max. system speed is approximately 110% of (LF.20)
When LF.2 = 4 then: 0 ... ±10V = 0 ... ± max. system speed (LF.20)
= Digital Speed Selection
= Analog Torque Control
= Analog Speed Control
= Serial Com. Speed Control
Direction Selection
terminals X2A.14,
X2A.15
terminal X2A.14,
does not determine direction
used only for triggering the
start sequence
terminals X2A.14 &
X2A.15
does not determine
U
direction.
sed only for
triggering the start sequence
Serial communication
16 bit control word