Equations: Operators - Notifier 1010 Installation And Programming Manual

Intelligent fire detection and alarm system
Hide thumbs Also See for 1010:
Table of Contents

Advertisement

P
56
AGE
C.B.E E
: O
QUATIONS
OR
Operator:
The first (and most useful) operator is OR.
Equation:
OR(Z9 Z15 Z23)
If ANY one of the three operand's in the equation
are in alarm, then the control module will be activated.
IF Software Zone 9 is in alarm OR
IF Software Zone 15 is in alarm OR
IF Software Zone 23 is in alarm,
THEN this control module will be activated.
AND
Operator:
The AND operator requires that each operand be in alarm.
Equation:
AND(Z9 Z15 Z23)
ALL three operand's in the equation MUST be
in alarm for the control module to be activated.
IF Software Zone 9 is in alarm AND
IF Software Zone 15 is in alarm AND
IF Software Zone 23 is in alarm,
THEN this control module will be activated.
NOT
Operator:
The NOT operator inverts the state of the operand (activated to deactivated OR
deactivated to activated).
Equation:
NOT(Z2)
The control module will remain activated UNTIL
the operand comes into alarm.
IF Software Zone 2 is in alarm,
THEN this control module will be deactivated.
PERATORS
C
OPYRIGHT
© 2000, N
I
P
OTIFIER
NERTIA
TY
1010/2020 I
A
NSTALLATION
L
TD
P
M
ND
ROGRAMMING
ANUAL