PPLICATION OF
It's required that all fan controls utilise Two CMX-2's (with tabs broken) and One MMX-101 per fan.
When installing the modules on the SLC loop, always make the address on the Start CMX-2 lower
numerically than the Stop CMX-2.
eg:
CMX-2 Start
CMX-2 Stop
MMX-101 Airflow
NOTE:
For programming Fan Controls please consult the Programming section of the Manual
M
ODULES
3
+24
FTR
9
8
7
6
COM
5
N/C
+24
FAN START
POWER
RUN
FR
No.
Revision - revise on CAD. Do not amend by hand
Eng. App.
3
C
M
AN
ONTROL
ODULES
= L1M1
= L1M2
= L1M3
C
OPYRIGHT
4
5
+ ANALOGUE LOOP
- ANALOGUE LOOP
FAN START
9
CMX-2
1
(-)
DATA
8
2
(+)
DATA
7
3
6
COM
4
5
N/C
N/O
TABS TO BE BROKEN
FAN STOP
STOP
FS
Copyright
This document is & shall
remain the property of
O
Notifier Inertia Fire Systems
C
Unauthorised use of this
document in any way is
prohibited.
Drawing File No.
E:\JOBS\..\Nifs_fan.sch
Date
4
5
© 2000, N
I
OTIFIER
NERTIA
1010/2020 I
NSTALLATION
6
FAN STOP
9
CMX-2
1
(-)
DATA
8
2
(+)
DATA
7
3
6
COM
4
5
N/C
N/O
TABS TO BE BROKEN
INDICATION
RUN [ CLOSED CCT ]
STOP [ 47K RES ]
FAULT [ OPEN CCT ]
COMM
RUN
FAULT
47K
47K
SEE NOTE A
SEE NOTE B
AFR
PFR
TYPICAL FAN INDICATION CONTACT ARRANGEMENT
7 Columbia Court,
1
Of:
Sheet:
Norwest Business Park
Drawn/
Baulkham Hills NSW 2153
25/2/00
Traced
AUSTRALIA
Tel
61 2 9894 1444
Approved
Fax
61 2 9899 4156
This Drawing must not be used for Construction
Email: support@inertia.com.au
unless signed as approved
6
P
L
TY
TD
A
P
M
ND
ROGRAMMING
ANUAL
7
8
D
INDICATION
(-)
BLACK
RED
(+)
MMX-101
(+)
VIOLET
(-)
YELLOW
C
B
NOTE :
USE ONLY RESISTOR A OR B
(A) = FAULT CONTACT NOT USED
(B) = FAULT CONTACT USED
LEGEND
AFR
SR
=START RELAY
AFR =AIR FLOW RELAY
SR
FR
= FAN RUN RELAY
FS
= FAN STOP RELAY
PFR = PHASE FAILURE RELAY
PFR
FTR = FIRE TRIP RELAY