Type Id (1=Typid); Control -B Y -Event 2=Cbe) - Notifier 1010 Installation And Programming Manual

Intelligent fire detection and alarm system
Hide thumbs Also See for 1010:
Table of Contents

Advertisement

1010/2020 I
A
NSTALLATION
ND
T
ID (1=TYPID)
YPE
Option 1 of the Partial Point Programming Menu allows the programmer to change the Software
Type ID of any detector, module, zone or Annunciator point. The following display illustrates the
assignment of the Software Type ID SCON to the 14th monitor module on Loop 3.
Select 1 from the Partial Point Programming Sub Menu.
ENTER LXX(D/M)YY,.ZXXX OR AXXPYY FOR PT CHANGE
(BCKSPC TO ABORT)
ENTER TYPE ID
C
-B
-E
ONTROL
Y
VENT
Option 2 of the Partial Point Programming Sub-Menu allows the programmer to change the Control-
By-Event (CBE) for any detector, module or software zone. The panel maintains a CBE for each
device and zone installed in the system.
NOTE: A software zone is not a physical zone, but rather software grouping in control panel
memory.
When programming a particular device, the control panel prompts the programmer with:
The following screen display illustrates CBE programming for smoke detector number 23 on Loop 2
to activate software zones 15 and 29.
Select 2 from the Partial Point Programming Sub Menu.
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT CHANGE
(BACK SPACE TO ABORT)
ENTER CONTROL-BY-EVENT*
*The open and close bracket and the space between the Z15 & Z19 are critical.
P
M
ROGRAMMING
ANUAL
(2=CBE)
ENTER.CONTROL-BY-EVENT
C
OPYRIGHT
© 2000, N
I
P
OTIFIER
NERTIA
TY
L
TD
P
45
AGE
L3M14
SCON.
L2D23
(Z15 Z29)