Ldm-32 Led Driver Annunciator; Lcd-80 Lcd Mimic Nnunciator Ual Ode In Acs Mode; Mode - Notifier 1010 Installation And Programming Manual

Intelligent fire detection and alarm system
Hide thumbs Also See for 1010:
Table of Contents

Advertisement

1010/2020 I
A
NSTALLATION
ND
LDM-32 LED D
RIVER
SW3
ON
1
N/A
2
Expander Installed
3
N/A
4
N/A
5
Receive Only Mode
6
Piezo Disabled
7
Lamp Test Enabled
8
LED's to Come on
Steady
SW3-8 must be on, when used in conjunction with an LDM32R(Relay Board)
SW4 (Slide Switch On PCB, must always be set to the left)
LCD-80 LCD M
IMIC
SW1
ON
1
Receive Only
2
Australian Time & Date
3
Piezo Disabled
4
Disable Keys
5
N/A
6
Always On
7
N/A
8
N/A
Annunciator Tens Addressing - SW3
Tens Digit
SW3-1
0
OFF
1
ON
2
OFF
3
ON
Annunciator Units Addressing – SW2
SW2
Use Rotary Dial For
Annunciator Units Digit.
EG: Annunciator Address 25 would be
Note: In the above configuration the LCD-80 in ACS mode will use its Annunciator address and the
NEXT Annunciator address. In this mode, you can have 128 Messages of 40 Characters in length.
For other combinations please contact Notifier/Inertia.
P
M
ROGRAMMING
ANUAL
A
NNUNCIATOR
A
NNUNCIATOR
SW3-2
OFF
OFF
ON
ON
C
OPYRIGHT
OFF
Always Use This Setting
Expander Not Installed
Always Use This Setting
Always Use This Setting
Normal Mode
Piezo Enabled
Lamp Test Disabled
LED's to Flash (until Acknowledged)
(D
M
)
ACS
UAL
ODE
IN
OFF
Normal Mode
USA Time & Date
Piezo Enabled
Enable Keys
Always Off
N/A
ACS Mode Enabled
Always Off
SW3-1 = OFF
SW3-2 = ON
SW2 = 5