Fire Floor, Floor Above, Floor Below
Example # 4:
L1D1 activates Z1 and Z2.
L1D2 activates Z1, Z2 and Z3.
L1D3 activates Z2, Z3 and Z4.
L1M1 will activate when Z1 is active.
L1M2 will activate when Z2 is active.
L1M3 will activate when Z3 is active.
L1M4 will activate when Z4 is active.
Different C.B.E same result
The following example shows the flexibility of C.B.E mapping from a detector to a CMX-2
Control module:
Solution A shows the use of a Zone to communicate from the detector to the Module.
Solution B shows the module looking at the detector.
Solution C shows the detector controlling the module.
Note the C.B.E equations.
Note: Monitor modules could be used in place of detectors.