Example: Programming Monitor Modules
Monitor Module 15 on Loop 3 is an MMX-2 and is to be programmed to monitor a full zone of
conventional smoke detectors, activate software zone (Z13), and is also mapped to Annunciator
address "02" point "03".
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT INSTALL
(BCKSPC TO ABORT)
ENTER TYPE ID
ENTER CONTROL-BY-EVENT
ENTER 20 CHARACTER CUSTOM LABEL
IS THE TRACKING OPTION TO BE DE-ISOLATED FOR THIS
DEVICE? (Y=YES, N=NO).
DO YOU WANT THIS POINT MAPPED TO AN ANNUNCIATOR?
(Y=YES,N=NO)
ENTER AXXPYY FOR ANNUNCIATOR POINT MAPPING
Example: Programming Control Modules
Control Module 19 on Loop 2 is to be programmed to be a relay output and turn on in response to
an alarm condition on either of two software zones (Z13 or Z29), and also mapped to Annunciator
address "02" point "04". Also as this output is a bell we want to set the bell isolate and walk test
flags.
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT INSTALL
(BCKSPC TO ABORT)
ENTER TYPE ID
ENTER.CONTROL-BY-EVENT
ENTER 20 CHARACTER CUSTOM LABEL
IS THE BELL ISOLATE OPTION TO BE ENABLED FOR THIS
DEVICE? (Y=YES,N=NO)
IS THE WALK TEST OPTION TO BE ENABLED FOR THIS
DEVICE? (Y=YES,N=NO)
DO YOU WANT THIS POINT MAPPED TO AN ANNUNCIATOR?
(Y=YES,N=NO)
ENTER AXXPYY FOR ANNUNCIATOR POINT MAPPING
C
© 2000, N
OPYRIGHT
OTIFIER
1010/2020 I
NSTALLATION
BASEMENT DETECTORS
MAIN LOBBY BELL
I
P
L
NERTIA
TY
TD
A
P
M
ND
ROGRAMMING
ANUAL
L3M15
SCON
(Z13)
N
Y
A2P3
L2M19
FORC
OR(Z13 Z29)
Y
Y
Y
A2P4

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Notifier 1010

This manual is also suitable for:

2020

Table of Contents